ABB TruONE ATS Installation And Operating Instruction page 65

Automatic transfer switches
Table of Contents

Advertisement

3 4 O X _ 3 0 - 1 6 0 0 r e v. B / 1 S C C 3 0 3 0 1 1 M 0 2 0 1
Parameters (continued)
Device Parameters (continued)
Manual Retransfer
Commit Transfer
Transfer to Dead Source
Off*
On
Off*
On
On*
Off
Automatic retransfer sequence enabled. Load is
automatically retransferred to priority source
upon the restoration of priority source.
Automatic retransfer sequence disabled. Load will
be kept on non-priority source until operator
manually (by HMI or manual handle) or remotely
operates the load back to priority source. Load is
also retransferred when the feature is set OFF.
If priority source fails, device cancels the transfer
sequence to non-priority source (generator) if
priority source returns before non-priority source
becomes acceptable.
If priority source fails, device continues transfer
sequence to non-priority source (generator) even
if priority returns before non-priority source
becomes acceptable. Retransfer sequence
according to time delays.
User can transfer to an unavailable source by using
HMI keys I/II or by a remote command.
Transfer to an unavailable source is disabled.