Tr u O N E ® AT S , I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N
2.3 TruONE® ATS feature comparison
Feature comparison
Ampere sizes available
Rated voltage
Rated frequency
Phase system
Number of poles
Neutral configuration
Switched
Overlapping
Product type
Open transition (I-II or II-I)
Delayed transition
(I - O - II or II - O - I)
Voltage and frequency settings
Pick up Voltage Source 1
Drop out Voltage Source 1
Pick up Voltage Source 2
Drop out Voltage Source 2
Pick up Frequency Source 1
Drop out Frequency Source 1
Pick up Frequency Source 2
Drop out Frequency Source 2
Time delay settings
Override momentary
Source 1 Outage, sec
Transfer from source 1
to source 2, sec
Override momentary
Source 2 Outage, sec
Level 2 controls (DIP) Level 3 controls (LCD) Level 4 controls (TOUCH)
S1
S2
S1
O
S2
l
ll
!
l
ll
!
LOAD
AUTO
LOAD
AUTO
Auto
In-phase
Priority
Manual
Auto
In-phase
Priority
Manual
config
monitor
retransfer
config
monitor
retransfer
Start
On
No priority
On
Start
On
No priority
On
Ok
Off
Source 1
Off
Ok
Off
Source 1
Off
Dropout ∆U / ∆f
∆U 5% / ∆f 5%
Dropout ∆U / ∆f
∆U 5% / ∆f 5%
∆U 10% / ∆f 5%
∆U 10% / ∆f 5%
∆U 15% / ∆f 10%
∆U 15% / ∆f 10%
∆U 20% / ∆f 10%
∆U 20% / ∆f 10%
Generator
Center
Generator
stop delay
/OFF
stop delay
delay
S1 Failure
S1 Return
S1 Failure
S1 Return
delay [s]
delay [min]
delay [s]
delay [min]
0
2
4
10
20
30 s
0 s
0
2
4
10
20
30 s
1
3
5
15
30
4 min
4 s
1
3
5
15
30
4 min
Off
On
Bypass
Off
On
Bypass
Lamp
Auto
Lamp
Auto
load
load
time
load
load
time
test
test
test
test
delay
Alarm reset
test
test
delay
Alarm reset
l
O
ll
l
ll
ON
OFF
ON
ON
ON
IEC: 200...1600 A
UL: 30...1200 A
200...480 Vac
50 / 60 Hz
1 / 2 / 3
2, 3 and 4
Yes
No
Yes
Yes
Fixed 2% above drop
out
+/-5, 10, 15, 20%
Fixed 2% above drop
out
+/-5, 10, 15, 20%
Fixed 1% above drop
out
+/-5, 10%
Fixed 1% above drop
out
+/-5, 10%
0, 1, 2, 3, 4, 5, 10, 15,
20, 30
2 (0...3600 via Ekip
Connect)
1,5 (0...60 via Ekip
Connect)
S1
O
S2
S1
S2
l
ll
!
l
ll
!
LOAD
AUTO
LOAD
AUTO
Auto
Auto
Esc
Esc
Alarm reset
Alarm reset
l
O
ll
l
ll
ON
OFF
ON
ON
ON
IEC: 200...1600 A
UL: 30...1200 A
200...480 Vac
50 / 60 Hz
1 / 2 / 3
2, 3 and 4
Yes
Yes
Yes
Yes
71...99%, 101...119%
70...98%, 102...120%
71...99%, 101...119%
70...98%, 102...120%
80,5...99,5%,
100,5...119,5%
80...99%, 101...120%
80,5...99,5%,
100,5...119,5%
80...99%, 101...120%
0...60
0...3600
0...60
S1
O
S2
S1
S2
ll
ll
l
!
l
!
LOAD
AUTO
LOAD
AUTO
l
O
ll
l
ll
ON
OFF
ON
ON
ON
IEC: 200...1600 A
UL: 30...1200 A
200...480 Vac
50 / 60 Hz
1 / 2 / 3
3 and 4
Yes
Yes
Yes
Yes
71...99%, 101...119%
70...98%, 102...120%
71...99%, 101...119%
70...98%, 102...120%
80,5...99,5%,
100,5...119,5%
80...99%, 101...120%
80,5...99,5%,
100,5...119,5%
80...99%, 101...120%
0...60
0...3600
0...60