Automatic transfer switch, I/O contacts
Generator start/stop
1
2
3
G
C
NO NC
Output relay features
Common, voltage supply
1
2
3
5
6
NO NC
C
O1
C
Fire Fighting applications
6
10
11
12
13
-
+
FIRE
24V
O1
C
Input contact features
Common input
10
11
12
13
-
+
FIRE
24V
C
I1
10
11
12
13
14
-
+
FIRE
24V
C
I1
I2
13
15
10
11
12
14
-
+
FIRE
24V
C
I1
I2
I3
3 4 O X _ 3 0 - 1 6 0 0 r e v. B / 1 S C C 3 0 3 0 1 1 M 0 2 0 1
Common, voltage supply
5
6
10
Generator start/stop NO
Generator start/stop NC
+
FIRE
24V
C
O1
Level 2
10
11
12
13
Alarm/Product available
Level 3 and 4
-
+
FIRE
24V
C
I1
Programmable output
(default; Alarm/Product
available)
Fire fighting input 24 Vdc (+)
14
Fire fighting input 24 Vdc (-)
I1
I2
Level 2
Emergency stop
Level 3
Programmable input
(default; Emergency stop)
Programmable input
(default; Remote test on load)
Level 4
Programmable input
(default; Emergency stop)
Programmable input
(default; Remote test on load)
Programmable input
(default; Remote test off load)
Cable size: 0.5...2.5 mm
24...14 AWG
11
12
13
-
C
I1
Cable size: 0.5...2.5 mm
24...14 AWG
Cable size: 0.5...2.5 mm
24...14 AWG
Cable size: 0.5...2.5 mm
24...14 AWG
Cabling
Stripping length; 6,5 mm, 0,255"
2
1 5 A@250 Vac (AC-1), 5 A@30 Vdc
2
3
2
5 5 A@250 Vac (AC-1), 5 A@30 Vdc
Level 2 = HMI with DIP-switches
6
Level 3 = HMI with LCD screen,
Level 4 = HMI with touch screen
6
2
Only in OXB_-types, delayed
transition, I – O – II or II – O – I
10
11
Do not connect to any
2
12
Level 2 = HMI with DIP-switches
13
Only in OXB_-types, delayed
transition, I – O – II or II – O – I
Level 3 = HMI with LCD screen
13
14
Only in OXB_-types, delayed
transition, I – O – II or II – O – I
Level 4 = HMI with touch screen
13
14
15
Only in OXB_-types, delayed
transition, I – O – II or II – O – I
117
Rating / Remark
SELV
power supply
24 Vdc 5 mA