Tr u O N E ® AT S , I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N
Settings (*Default) (continued)
Modules (Optional modules) (continued)
Ekip Signalling 2K-1 / -2 / -3 (continued)
O 11/12, O 21/22, O 31/32 (continued)
Function (continued)
Contact
Type
Test
:
Modules (Optional modules)
Ekip Signalling 2K-1 / -2 / -3
:
Table 5.5 Configuration and test parameters of Ekip Signalling 2K-_ -module in HMI
The following table illustrates the path
from the display for accessing informa-
tion on the module:
About
:
Modules (Optional modules)
Ekip Signalling 2K-1 / -2 / -3
SN
Version
Input 1
Input 2
Output 1
Output 2
:
Table 5.4 Information of Ekip Signalling 2K-_ -module in HMI
Source 1 Available
Source 2 Available
Load Shed 1
Elevator pre-signal
NC
NO*
Description
No anomalies in S1 voltage supply.
No anomalies in S2 voltage supply.
Used for shedding non-essential loads before
transferring to non-priority source. Signal is activated
before transferring to non-priority source according to
load shed delay and kept activated until load is
transferred back to priority source.
Signal is activated and transfer is delayed according to
Elevator pre-signal delay. Signal is kept activated
according to Elevator post-signal delay after transfer.
Active open
Active closed
Auto Test
Description
Serial number
Software version
The logical state of the inputs:
"Off" if not active, "On" if active
The state of the output contacts:
"Open" if open, "Closed" if closed