3 4 O X _ 3 0 - 1 6 0 0 r e v. B / 1 S C C 3 0 3 0 1 1 M 0 2 0 1
8.2.4 Phase barriers
Phase barriers must be used between the
LOAD side terminals of TruONE automatic
transfers switches with switch types
OX_400U/500E...1200U/1600E. These
switch types include the phase barriers
for LOAD side from the factory. Additional
phase barriers to be used for the SOURCE
side terminals must be ordered separately
when needed.
8.3 Clearances per UL1008
A
Fig. 8.10 UL standard switches, clearances per UL1008
Size (Current)
OX_30...200U_
OX_260...400U_
OX_600U_
OX_800U_ ...OX_1200U_
Minimum enclosure size or equivalent volume
Size (Current)
OX_30...200U_
OX_260...400U_
OX_600U_
OX_800U_ ...OX_1200U_
C
B
C
A [in /mm]
1 / 26
1 / 26
1 / 26
1 / 26
Width [in /mm]
23.6 / 600
23.6 / 600
23.6 / 600
31.5 / 800
Fig. 8.9 Mounting of phase barriers.
B [in /mm]
D [in /mm]
0.5 / 13
0.5 / 13
0.5 / 13
0.5 / 13
0.5 / 13
0.5 / 13
0.5 / 13
0.5 / 13
Height [in /mm]
31.5 / 800
31.5 / 800
31.5 / 800
39.4 / 1000
133
D
C
According to the
UL1008 standard
Depth [in /mm]
11.8 / 300
11.8 / 300
11.8 / 300
11.8 / 300