Particulate and gaseous contamination specifications

The following table defines the limitations that help avoid any equipment damage or failure from particulate and gaseous contamination. If
the levels of particulate or gaseous pollution exceed the specified limitations and result in equipment damage or failure, you may need to
rectify the environmental conditions. Remediation of environmental conditions is the responsibility of the customer.
Table 35. Particulate contamination specifications
Particulate contamination
Air filtration
Conductive dust
Corrosive dust
Table 36. Gaseous contamination specifications
Gaseous contamination
Copper coupon corrosion rate
Silver coupon corrosion rate
NOTE:
Maximum corrosive contaminant levels measured at ≤50% relative humidity.
42
Technical specifications
CPU Thermal
CPU heat sink
Design Power
(TDP)
150 W/8 core, 165
1U high
W/12 core, 200
performance
W, 205 W
Specifications
Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with a
95% upper confidence limit.
NOTE:
environments only. This air filtration requirement does not apply to
IT equipment designed to be used outside a data center, in
environments such as an office or factory floor.
NOTE:
filtration.
Air must be free of conductive dust, zinc whiskers, or other conductive
particles.
NOTE:
environments.
Air must be free of corrosive dust.
Residual dust present in the air must have a deliquescent point less than
60% relative humidity.
NOTE:
environments.
Specifications
<300 Å/month per Class G1 as defined by ANSI/ISA71.04-2013.
<200 Å/month as defined by ANSI/ISA71.04-2013.
Fan type
GPU
High performance
≥1 double-width/
fan
single-width
The ISO Class 8 condition applies to data center
Air entering the data center must have MERV11 or MERV13
This condition applies to data center and non-data center
This condition applies to data center and non-data center
Ambient
restriction
30°C