i.8 Parameter Table
No.
Name
b5-07
PID Offset Adjustment
Feedback Loss 4 to 20
b5-12
mA Detection
Selection
Feedback Loss Goto
b5-13
Frequency
Feedback Loss of
b5-14
Prime Level
Feedback Loss Go To
b5-15
Frequency Time Out
Feedback Loss Start
b5-16
Delay
b5-32
Integrator Ramp Limit
PID Setpoint Display
b5-39
Digits
C1-01
Acceleration Time 1
C1-02
Deceleration Time 1
C1-03
Acceleration Time 2
C1-04
Deceleration Time 2
S-Curve Characteristic
C2-01
at Accel Start
S-Curve Characteristic
C2-02
at Accel End
S-Curve Characteristic
C2-03
at Decel Start
S-Curve Characteristic
C2-04
at Decel End
Carrier Frequency
C6-02
Selection
d1-01 to
Frequency Reference 1
d1-16
to 16
Jog Frequency
d1-17
Reference
Frequency Reference
d2-01
Upper Limit
88
Description
Applies an offset to the PID controller
output. Set as a percentage of the maximum
output frequency.
0: Disabled
1: Alarm only
2: Fault
3: Run at b5-13
Sets the speed at which the drive will run if
a 4 to 20 mA wire break is detected on the
PID Feedback and when b5-12 is set to 3
(Run at b5-13).
Detects loss of prime in the pump when a
wire break condition has occurred.
When b5-12 = 3 and the Feedback signal is
lost, the drive will run at the b5-13 speed for
the b5-15 time, after which the drive will
fault on Feedback Loss (FDBKL).
When an AUTO Run command is initiated,
the drive will not fault on Feedback Loss
(FDBKL) or use the Feedback Loss GoTo
Frequency (b5-13) until the b5-16 time has
expired.
When set to a value greater than zero, the PI
Integrator is forced to be within +/- this
amount of the soft starter output.
0: No decimal places
1: One decimal place
2: Two decimal places
3: Three decimal places
Sets the time to accelerate from 0 to
maximum frequency.
Sets the time to decelerate from maximum
frequency to 0.
Sets the time to accelerate from 0 to
maximum frequency.
Sets the time to decelerate from maximum
frequency to 0.
The S-curve can be controlled at the four
points shown below.
ON
OFF
Run Command
Output Frequency
C2-02
C2-03
C2-01
1: 2.0 kHz
2: 5.0 kHz (4.0 kHz)
3: 8.0 kHz (6.0 kHz)
4: 10.0 kHz (8.0 kHz)
5: 12.5 kHz (10.0 kHz)
6: 15.0 kHz (12.0 kHz)
7: Swing PWM1 (1.5 to 2.5 kHz Random)
8: Swing PWM2 (1.0 to 3.0 kHz Random)
9: Swing PWM3 (1.5 to 2.5 kHz Sinusoidal)
A: Swing PWM4 (1.5 to 2.5 kHz
Sinusoidal)
B to E: No setting possible
F: User-defined (determined by C6-03
through C6-05)
Sets the frequency reference for the drive.
Setting units are determined by parameter
o1-03.
Sets the Jog frequency reference. Setting
units are determined by parameter o1-03.
Sets the frequency reference upper limit as
a percentage of the maximum output
frequency.
YASKAWA TOEP YAIP1W 02E YASKAWA AC Drive - iQpump1000 Installation & Start-up Guide
No.
Name
Frequency Reference
d2-02
Lower Limit
Master Speed
d2-03
Reference Lower Limit
d3-01 to
Jump Frequency 1 to 3
d3-03
d3-04
Jump Frequency Width
E1-01
Input Voltage Setting
E1-03
V/f Pattern Selection
Maximum Output
E1-04
C2-04
Frequency
Time
E1-05
Maximum Voltage
E1-06
Base Frequency
Middle Output
E1-07
Frequency
Middle Output
E1-08
Frequency Voltage
Minimum Output
E1-09
Frequency
Minimum Output
E1-10
Frequency Voltage
Middle Output
E1-11
Frequency 2
Middle Output
E1-12
Frequency Voltage 2
E1-13
Base Voltage
E2-01
Motor Rated Current
E2-02
Motor Rated Slip
Motor No-Load
E2-03
Current
Description
Sets the frequency reference lower limit as
a percentage of the maximum output
frequency.
Sets the lower limit for frequency
references from analog inputs as a
percentage of the maximum output
frequency.
Eliminates problems with resonant
vibration of the motor/machine by avoiding
continuous operation in predefined
frequency ranges. The drive accelerates and
decelerates the motor through the
prohibited frequency ranges.
Parameters must be set so that d3-01 ≥
d3-02 ≥ d3-03.
Sets the dead-band width around each
selected prohibited frequency reference
point.
This parameter must be set to the power
supply voltage.
WARNING! Electrical Shock Hazard.
Drive input voltage (not motor
voltage) must be set in E1-01 for the
protective features of the drive to
function properly. Failure to do so
may result in equipment damage
and/or death or personal injury.
0: 50 Hz, Constant torque 1
1: 60 Hz, Constant torque 2
2: 60 Hz, Constant torque 3 (50 Hz base)
3: 72 Hz, Constant torque 4 (60 Hz base)
4: 50 Hz, Variable torque 1
5: 50 Hz, Variable torque 2
6: 60 Hz, Variable torque 3
7: 60 Hz, Variable torque 4
8: 50 Hz, High starting torque 1
9: 50 Hz, High starting torque 2
A: 60 Hz, High starting torque 3
B: 60 Hz, High starting torque 4
C: 90 Hz (60 Hz base)
D: 120 Hz (60 Hz base)
E: 180 Hz (60 Hz base)
F: Custom V/f, E1-04 through E1-13
settings define the V/f pattern
These parameters are only applicable when
E1-03 is set to F.
To set linear V/f characteristics, set the
same values for E1-07 and E1-09.
In this case, the setting for E1-08 will be
disregarded. Ensure that the four
frequencies are set according to these rules:
E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
Output Voltage (V)
E1-05
E1-12
E1-13
E1-08
E1-10
E1-09
E1-07 E1-06 E1-11 E1-04
Frequency (Hz)
Sets the motor nameplate full load current
in amps. Automatically set during
Auto-Tuning.
Sets the motor rated slip. Automatically set
during Auto-Tuning.
Sets the no-load current for the motor.
Automatically set during Auto-Tuning.