YASKAWA iQpump1000 Installation & Start?Up Manual page 101

Intelligent pump controller
Hide thumbs Also See for iQpump1000:
Table of Contents

Advertisement

WARNING! Electrical Shock Hazard. Because the leakage current exceeds 3.5 mA in models 4A0414 to 4A1200, IEC/EN
61800-5-1 states that either the power supply must be automatically disconnected in case of discontinuity of the protective earthing
conductor, or a protective earthing conductor with a cross-section of at least 10 mm
comply may result in death or serious injury.
A – Braided shield cable
B – Metal panel
6.
Connect a DC link choke to minimize harmonic distortion.
YASKAWA TOEP YAIP1W 02E YASKAWA AC Drive - iQpump1000 Installation & Start-up Guide
C
B
C – Cable clamp (conductive)
Figure i.35 Ground Area
i.9 Standards Compliance
2
2
(Cu) or 16 mm
(Al) must be used. Failure to
A
101