YASKAWA iQpump1000 Installation & Start?Up Manual page 32

Intelligent pump controller
Hide thumbs Also See for iQpump1000:
Table of Contents

Advertisement

i.4 Electrical Installation
n
Three-Phase 600 V Class
Drive Model
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
5A0003
⊖, ⊕1, ⊕2
5A0004
5A0006
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
⊖, ⊕1, ⊕2
5A0009
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
⊖, ⊕1, ⊕2
5A0011
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
⊖, ⊕1, ⊕2
5A0017
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
⊖, ⊕1, ⊕2
5A0022
B1, B2
32
Table i.6 Wire Gauge and Torque Specifications (Three-Phase 600 V Class)
Recomm. Gauge
Terminal
mm
Wire Range
2
(AWG, kcmil)
mm
2
(AWG, kcmil)
2.5
2.5 to 6.0
(14)
(14 to 10)
2.5
2.5 to 6.0
(14)
(14 to 10)
2.5 to 6.0
(14 to 10)
2.5 to 6.0
(14 to 10)
6.0
2.5 to 6.0
(10)
(14 to 10)
2.5
2.5 to 6.0
(14)
(14 to 10)
2.5
2.5 to 6.0
(14)
(14 to 10)
2.5 to 6.0
(14 to 10)
2.5 to 6.0
(14 to 10)
6.0
4.0 to 6.0
(10)
(12 to 10)
6.0
2.5 to 16
(10)
(14 to 6)
2.5
2.5 to 16
(14)
(14 to 6)
2.5 to 16
(14 to 6)
2.5 to 6.0
(14 to 10)
10
4.0 to 6.0
(8)
(12 to 8)
6.0
6.0 to 16
(10)
(10 to 6)
6.0
6.0 to 16
(10)
(10 to 6)
6.0 to 16
(10 to 6)
6.0 to 10
(10 to 8)
10
6.0 to 10
(8)
(12 to 8)
10
6.0 to 16
(8)
(10 to 6)
6.0
6.0 to 16
(10)
(10 to 6)
6.0 to 16
(10 to 6)
6.0 to 10
(10 to 8)
10
6.0 to 10
(8)
(10 to 6)
YASKAWA TOEP YAIP1W 02E YASKAWA AC Drive - iQpump1000 Installation & Start-up Guide
Screw
Tightening Torque
Size
N·m (lb.in.)
1.2 to 1.5
M4
(10.6 to 13.3)
1.2 to 1.5
M4
(10.6 to 13.3)
2.1 to 2.3
M4
(18.6 to 20.4)
2.0 to 2.5
M5
(17.7 to 22.1)
3.6 to 4.0
(31.8 to 35.4)
M5
2.7 to 3.0
(23.9 to 26.6)
5.4 to 6.0
M6
(47.8 to 53.1)
3.6 to 4.0
(31.8 to 35.4)
M5
2.7 to 3.0
(23.9 to 26.6)
5.4 to 6.0
M6
(47.8 to 53.1)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cimr-pw*a series

Table of Contents