i.4 Electrical Installation
n
Wire Size and Torque Specifications
Select appropriate wire type and gauges from
ends.
Screw
Terminal
Size
S1-S8, SC, SN, SP
RP, V+, A1, A2, A3,
AC, 24 V
MA, MB, MC, MD, ME,
M3
MF
M1-M4
FM, AM, AC
R+, R-, S+, S-, IG
u
Wiring the Control Circuit Terminal
This section describes the proper procedures and preparations for wiring the control terminals.
WARNING! Electrical Shock Hazard. Do not remove covers or touch the circuit boards while the power is on. Failure to comply could result
in death or serious injury.
NOTICE: Separate control circuit wiring from main circuit wiring (terminals R/L1, S/L2, T/L3, B1, B2, U/T1, V/T2, W/T3,
other high-power lines. Improper wiring practices could result in drive malfunction due to electrical interference.
NOTICE: Separate wiring for digital output terminals MA, MB, MC, MD, ME, MF and M1 to M4 from wiring to other control circuit lines.
Improper wiring practices could result in drive or equipment malfunction or nuisance trips.
NOTICE: Use a class 2 power supply when connecting to the control terminals. Improper application of peripheral devices could result in
drive performance degradation due to improper power supply. Refer to NEC Article 725 Class 1, Class 2, and Class 3 Remote-Control,
Signaling, and Power Limited Circuits for requirements concerning class 2 power supplies.
NOTICE: Insulate shields with tape or shrink tubing to prevent contact with other signal lines and equipment. Improper wiring practices could
result in drive or equipment malfunction due to short circuit.
NOTICE: Connect the shield of shielded cable to the appropriate ground terminal. Improper equipment grounding could result in drive or
equipment malfunction or nuisance trips.
NOTICE: Do not tighten screws beyond the specified tightening torque. Failure to comply may result in erroneous operation, damage to the
terminal block, or cause a fire.
NOTICE: Use shielded twisted-pair cables as indicated to prevent operating faults. Improper wiring practices could result in drive or
equipment malfunction due to electrical interference.
Wire the control circuit only after terminals have been properly grounded and main circuit wiring is complete.
Terminal Board Wiring Guide on page 39
23.
Refer to Wire Gauges on page
Connect control wires as shown in
38
Table
i.10. For simpler and more reliable wiring, use crimp ferrules on the wire
Table i.10 Wire Gauges
Bare Wire Terminal
Tightening
Torque
Applicable
N•m
wire size
(lb. in)
2
mm
(AWG)
Stranded wire:
0.2 to 1.0
0.5 to 0.6
(24 to 16)
(4.4 to 5.3)
Solid wire:
0.2 to 1.5
(24 to 16)
for details. Prepare the ends of the control circuit wiring as shown in
38.
Figure i.21
and
Figure
YASKAWA TOEP YAIP1W 02E YASKAWA AC Drive - iQpump1000 Installation & Start-up Guide
Ferrule-Type Terminal
Recomm.
Applicable
wire size
wire size
2
2
mm
(AWG)
mm
(AWG)
0.25 to 0.5
0.75 (18)
(24 to 20)
i.22.
Recomm.
Wire Type
wire size
2
mm
(AWG)
Shielded wire,
0.5 (20)
etc.
⊖ , ⊕ 1, ⊕ 2) and
Refer to
Figure i.