Drive Model
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
5A0027
⊖, ⊕1, ⊕2
5A0032
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
⊖, ⊕1
5A0041
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
⊖, ⊕1
5A0052
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
⊖, ⊕1
5A0062
⊕3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
⊖, ⊕1
5A0077
⊕3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
⊖, ⊕1
5A0099
⊕3
YASKAWA TOEP YAIP1W 02E YASKAWA AC Drive - iQpump1000 Installation & Start-up Guide
Recomm. Gauge
Terminal
mm
2
Wire Range
(AWG, kcmil)
mm
2
(AWG, kcmil)
16
16 to 25
(6)
(6 to 4)
16
16 to 25
(6)
(6 to 4)
16 to 25
–
(6 to 4)
6.0 to 10
–
(10 to 8)
16
10 to 16
(6)
(10 to 6)
16
6.0 to 25
(6)
(10 to 3)
16
6.0 to 25
(6)
(10 to 3)
–
(6 to 1)
4.0 to 25
–
(12 to 3)
16
10 to 16
(6)
(6)
25
6.0 to 25
(4)
(10 to 3)
16
6.0 to 25
(6)
(10 to 3)
16 to 35
–
(6 to 1)
10 to 25
–
(8 to 3)
16
10 to 16
(6)
(6)
25
6.0 to 95
(4)
(10 to 4/0)
25
6.0 to 95
(4)
(10 to 4/0)
25 to 95
–
(4 to 4/0)
16 to 95
–
(6 to 4/0)
25
25
(4)
(4)
25
6.0 to 95
(3)
(10 to 4/0)
25
6.0 to 95
(3)
(10 to 4/0)
25 to 95
–
(3 to 4/0)
16 to 95
–
(6 to 4/0)
25
25
(4)
(4)
70
6.0 to 95
(1/0)
(10 to 4/0)
50
6.0 to 95
(1)
(10 to 4/0)
35 to 95
–
(2 to 4/0)
25 to 95
–
(4 to 4/0)
25
25
(4)
(4)
i.4 Electrical Installation
Screw
Tightening Torque
Size
N·m (lb.in.)
5.4 to 6.0
M6
(47.8 to 53.1)
2.7 to 3.0
M5
(23.9 to 26.6)
5.4 to 6.0
M6
(47.8 to 53.1)
9.0 to 11
M8
(79.7 to 97.4)
9.0 to 11
M8
(79.7 to 97.4)
18 to 23
M10
(159 to 204)
18 to 23
M10
(159 to 204)
18 to 23
M10
(159 to 204)
33