<1> The setting range for the acceleration and deceleration times is determined by the accel/decel time setting units in C1-10. For example, if the time
is set in units of 0.01 s (C1-10 = 0), the setting range becomes 0.00 to 600.00 s.
n
E2-01: Motor Rated Current
Provides motor control, protects the motor, and calculates torque limits. Set E2-01 to the full load amps (FLA) stamped on
the motor nameplate. If Auto-Tuning completes successfully, the value entered to T1-04 will automatically be saved to E2-01.
No.
E2-01
<1> Display is in the following units:
2A0004 to 2A0040, 4A0002 to 4A0023, and 5A0007 to 5A0017: 0.01 A units.
2A0056 to 2A0415, 4A0031 to 4A0675, and 5A0022 to 5A0242: 0.1 A units.
4A0930 and 4A1200: 1 A units.
Note:
An oPE02 error will occur if E2-01 ≤ E2-03. Set E2-03 correctly to prevent this error.
n
E2-04: Number of Motor Poles
Set the number of motor poles to E2-04. If Auto-Tuning completes successfully, the value entered to T1-06 will automatically
be saved to E2-04.
No.
E2-04
n
H1-01 to H1-08: Functions for Terminals S1 to S8
These parameters assign functions to the multi-function digital inputs. The various functions and settings are listed in
i.22.
No.
H1-01
Multi-Function Digital Input Terminal S1 Function Selection
H1-02
Multi-Function Digital Input Terminal S2 Function Selection
H1-03
Multi-Function Digital Input Terminal S3 Function Selection
H1-04
Multi-Function Digital Input Terminal S4 Function Selection
H1-05
Multi-Function Digital Input Terminal S5 Function Selection
H1-06
Multi-Function Digital Input Terminal S6 Function Selection
H1-07
Multi-Function Digital Input Terminal S7 Function Selection
H1-08
Multi-Function Digital Input Terminal S8 Function Selection
<1> Number appearing in parenthesis is the default value after performing a 3-Wire initialization (A1-03 = 3330).
Setting
0
3-Wire sequence
2
External Reference 1/2 Selection
3
Multi-Step Speed Reference 1
4
Multi-Step Speed Reference 2
5
Multi-Step Speed Reference 3
6
Jog reference selection
7
Accel/decel time selection 1
8
Baseblock command (N.O.)
YASKAWA TOEP YAIP1W 02E YASKAWA AC Drive - iQpump1000 Installation & Start-up Guide
Parameter Name
Acceleration Time 1
Deceleration Time 1
Acceleration Time 2
Deceleration Time 2
Parameter Name
Motor Rated Current
Parameter Name
Number of Motor Poles
Parameter Name
Table i.22 Multi-Function Digital Input Terminal Settings
Function
i.5 Start-Up Programming and Operation
Setting
Range
1 to 9F
40 (F)
1 to 9F
F: Through Mode
0 to 9F
26: External Pump Fault
0 to 9F
14: Fault Reset
0 to 9F
8D (0)
0 to 9F
80 (3)
0 to 9F
81 (4)
0 to 9F
F (6)
Page
Setting
9
Baseblock command (N.C.)
A
Accel/decel ramp hold
B
Drive overheat alarm (oH2)
C
Analog terminal input selection
F
Through mode
10
Up command
11
Down command
12
Forward Jog
Setting Range
<1>
0.0 to 6000.0 s
Setting Range
10% to 200% of the drive
<1>
rated current
Setting Range
2 to 48
Default
<1>
: Forward Run Command (2-Wire sequence)
<1>
: Multi Setpoint 1
<1>
: HAND Mode
<1>
: HAND Mode 2
<1>
: Through Mode
Function
Default
10.0 s
Default
Determined by
o2-04
Default
2
Table
Page
59