Powering Up the Drive
Review the following table before applying power.
Item to Check
Power supply voltage
Drive output terminals and
motor terminals
Control circuit terminals
Drive control terminal status
Status of the load and connected
machinery
<1> Confirm the following when connecting models 4A0930 and 4A1200: Remove the jumpers on R1/L11, S1/L21, and T1/L31 when using 12-phase
rectification. When operating without 12-phase rectification, properly wire terminals R1/L11, S1/L21, and T1/L31 in addition to terminals R/L1,
S/L2, and T/L3.
u
Basic Drive Setup Adjustments
n
A1-01: Access Level Selection
Allows or restricts access to drive parameters.
No.
A1-01
Setting 0: Operation only
Access to only parameters A1-01, A1-04, and all U monitor parameters.
Setting 1: User Parameters
Access to only a specific list of parameters set to A2-01 through A2-32. These User Parameters can be accessed using the
Setup Mode of the digital operator.
Setting 2: Advanced Access Level (A) and Setup Access Level (S)
All parameters can be viewed and edited.
Setting 3: Lock Parameters
Parameters that are normally visible in the advanced access level (A1-01 = 2) are still visible, but the only parameters that can
be changed are A1-01 and A1-04.
The Auto Tuning and Pump Quick Setup menus will not be displayed.
n
A1-03: Initialize Parameters
Resets parameters to default values or performs an Application Preset for fan or pump applications. After initialization, the
setting for A1-03 automatically returns to 0.
No.
A1-03
Note:
1. Settings 6012 and 6013 are available in drive software versions PRG: 8552 and later.
2. Settings 6012 and 6013 are not available in drive models 4A0930 and 4A1200.
YASKAWA TOEP YAIP1W 02E YASKAWA AC Drive - iQpump1000 Installation & Start-up Guide
200 V class: Three-phase/Single-phase 200 to 240 Vac 50/60 Hz
400 V class: Three-phase/Single-phase 380 to 480 Vac 50/60 Hz
600 V class: Three-phase/Single-phase 500 to 600 Vac 50/60 Hz
Properly wire the power supply input terminals (R/L1, S/L2, T/L3).
Check for proper grounding of drive and motor.
Properly wire drive output terminals U/T1, V/T2, and W/T3 with motor terminals U, V, and W.
Check control circuit terminal connections.
Open all control circuit terminals (off).
Decouple the motor from the load.
Parameter Name
Access Level Selection
Parameter Name
Initialize Parameters
i.5 Start-Up Programming and Operation
Description
<1>
Setting Range
0 to 3
Setting Range
0, 1110, 2220, 3330, 5550,
6008, 6009, 6010, 6011,
6012, 6013, 6014, 7770,
7771
Note:
A1-03 is initially
set to "6008" from
the factory,
although the
keypad will
always display
"0".
Default
2
Default
0
51