i.5 Start-Up Programming and Operation
Setting 1110: User Initialize
Resets parameters to the values selected by the user as User Settings. User Settings are stored when parameter o2-03 is set to
"1: Set defaults".
Note:
User Initialization resets all parameters to a user-defined set of default values previously saved to the drive. Set parameter o2-03 to 2 to
clear the user-defined default values.
Setting 2220: 2-Wire Initialization
Resets parameters to default settings with digital inputs S1 and S2 configured as Forward run and Reverse run, respectively.
Setting 3330: 3-Wire Initialization
Resets parameters to default settings with digital inputs S1, S2, and S5 configured as Run, Stop, and Forward/Reverse
respectively.
Setting 5550: Terminal/Control Initialize
An oPE04 error appears on the digital operator when a terminal block with settings saved to its built-in memory is installed
in a drive that has edited parameters. Set A1-03 to 5550 to use the parameter settings saved to the terminal block memory.
Application Presets are available to facilitate drive setup for commonly used applications. Selecting one of these Application
Presets automatically assigns functions to the input and output terminals and sets a predefined group of parameters to values
appropriate for the selected application.
In addition, the parameters most likely to be changed are assigned to the group of User Parameters, A2-01 through A2-16.
User Parameters are part of the Setup Group, which provides quicker access by eliminating the need to scroll through multiple
menus.
Setting 6008: Pressure Control
Application Preset for Pressure Control applications.
Setting 6009: Pump Down Level
Application Preset for Pump Down Level applications.
Setting 6010: Geothermal Mode
Application Preset for Geothermal Mode.
Setting 6011: VTC Pressure Mode
Application Preset for VTC Pressure Mode.
Setting 6012: Pivot Panel VTC
Application Preset for Pivot Panel VTC.
Note:
1. This setting is available in drive software versions PRG: 8552 and later.
2. This setting is not available in drive models 4A0930 and 4A1200.
Setting 6013: Advanced Pressure Control
Application Preset for Advanced Pressure Control.
Note:
1. This setting is available in drive software versions PRG: 8552 and later.
2. This setting is not available in drive models 4A0930 and 4A1200.
Setting 6014: Pivot Panel Submersible
Application Preset for Pivot Panel Submersible Control.
Note:
1. This setting is available in drive software versions PRG: 8553 and later.
2. This setting is not available in drive models 4A0930 and 4A1200.
Setting 7770: General Purpose
General Purpose Application Preset.
Setting 7771: Submersible Motor General Purpose Operation
General Purpose Application Preset.
n
b1-01: Frequency Reference Selection 1
Selects the frequency reference source 1 for the REMOTE mode.
Note:
If a Run command is input to the drive but the frequency reference entered is 0 or below the minimum frequency, the RUN indicator LED
on the digital operator will light and the STOP indicator will flash.
52