YASKAWA iQpump1000 Installation & Start?Up Manual page 63

Intelligent pump controller
Hide thumbs Also See for iQpump1000:
Table of Contents

Advertisement

n
H3-05: Terminal A3 Signal Level Selection
Determines the function assigned to analog input terminal A3.
No.
H3-05
Setting 0: 0 to 10 Vdc
The input level is 0 to 10 Vdc. See the explanation provided for H3-01.
Setting 1: 0 to 10 Vdc Bipolar
The input level is -10 to 10 Vdc. See the explanation provided for H3-01.
62.
Setting 2: 4 to 20 mA
Setting 3: 0 to 20 mA
n
H3-06: Terminal A3 Function Selection
Determines the function assigned to analog input terminal A3.
No.
H3-06
n
H3-07, H3-08: Terminal A3 Gain and Bias Setting
Parameter H3-07 sets the level of the selected input value that is equal to 10 Vdc input at terminal A3 (gain).
Parameter H3-08 sets the level of the selected input value that is equal to 0 V input at terminal A3 (bias).
No.
H3-07
H3-08
n
H3-09: Terminal A2 Signal Level Selection
Selects the input signal level for analog input A2. Set Jumper S1 on the terminal board accordingly for a voltage input or
current input.
No.
H3-09
Setting 0: 0 to 10 Vdc
The input level is 0 to 10 Vdc.
Setting 1: 0 to 10 Vdc Bipolar
The input level is -10 to 10 Vdc.
Setting 2: 4 to 20 mA
The input level is 4 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.
Setting 3: 0 to 20 mA
The input level is 0 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.
n
H3-10: Terminal A2 Function Selection
Determines the function assigned to analog input terminal A2.
No.
H3-10
YASKAWA TOEP YAIP1W 02E YASKAWA AC Drive - iQpump1000 Installation & Start-up Guide
Name
Terminal A3 Signal Level Selection
Name
Terminal A3 Function Selection
Name
Terminal A3 Gain Setting
Terminal A3 Bias Setting
Name
Terminal A2 Signal Level Selection
Refer to Setting 0: 0 to 10 Vdc on page
Refer to Setting 1: 0 to 10 Vdc Bipolar on page
Name
Terminal A2 Function Selection
i.5 Start-Up Programming and Operation
Setting Range
0 to 3
Refer to Setting 0: 0 to 10 Vdc on page
Refer to Setting 1: 0 to 10 Vdc Bipolar on page
Setting Range
0 to 31
Setting Range
-999.9 to 999.9%
-999.9 to 999.9%
Setting Range
0 to 3
62.
62.
Setting Range
0 to 32
Default
0
62.
Default
20
Default
100.0%
0.0%
Default
2
Default
B
63

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for: