i.5 Start-Up Programming and Operation
n
H3-11, H3-12: Terminal A2 Gain and Bias Setting
Parameter H3-11 sets the level of the input value selected that is equal to 10 Vdc input or 20 mA input to terminal A2.
Parameter H3-12 sets the level of the input value selected that is equal to 0 V, 4 mA or 0 mA input at terminal A2.
Use both parameters to adjust the characteristics of the analog input signal to terminal A2. The setting works in the same way
as parameters H3-03 and H3-04 for analog input A1.
No.
H3-11
H3-12
n
H4-01, H4-04: Multi-Function Analog Output Terminal FM, AM Monitor Selection
Sets the desired drive monitor parameter Uo-oo to output as an analog value via terminal FM and AM. Refer to the drive
User Manual for a list of all monitors. The "Analog Output Level" column indicates whether a monitor can be used for analog
output.
Example: Enter "103" for U1-03.
No.
H4-01
Multi-Function Analog Output Terminal FM Monitor Selection
H4-04
Multi-Function Analog Output Terminal AM Monitor Selection
A setting of 031 or 000 applies no drive monitor to the analog output. With either of these settings, the output level of the
terminals FM and AM can be set by a PLC via a communication option or MEMOBUS/Modbus (through mode).
n
H4-02, H4-03: Multi-Function Analog Output Terminal FM Gain and Bias
H4-05, H4-06: Multi-Function Analog Output Terminal AM Gain and Bias
Parameters H4-02 and H4-05 set the terminal FM and AM output signal level when the value of the selected monitor is at
100%. Parameters H4-03 and H4-06 set the terminal FM and AM output signal level when the value of the selected monitor
is at 0%. Both are set as a percentage, where 100% equals 10 Vdc or 20 mA analog output and 0% equals 0 V or 4 mA. The
output voltage of both terminals is limited to +/-10 Vdc.
The output signal range can be selected between 0 to +10 Vdc or -10 to +10 Vdc, or 4 to 20 mA using parameter H4-07 and
H4-08.
No.
H4-02
Multi-Function Analog Output Terminal FM Gain
H4-03
Multi-Function Analog Output Terminal FM Bias
H4-05
Multi-Function Analog Output Terminal AM Gain
H4-06
Multi-Function Analog Output Terminal AM Bias
Using Gain and Bias to Adjust Output Signal Level
The output signal is adjustable while the drive is stopped.
n
H4-07, H4-08: Multi-Function Analog Output Terminal FM, AM Signal Level Selection
Sets the voltage output level of U parameter (monitor parameter) data to terminal FM and terminal AM using parameters
H4-07 and H4-08.
Set jumper S5 on the terminal board accordingly when changing these parameters.
Selection on page 43
for details on setting S5.
No.
H4-07
H4-08
Setting 0: 0 to 10 V
Setting 1: -10 V to 10 V
Setting 2: 4 to 20 mA
64
Name
Terminal A2 Gain Setting
Terminal A2 Bias Setting
Name
Name
Name
Multi-Function Analog Output Terminal FM
Signal Level Selection
Multi-Function Analog Output Terminal AM
Signal Level Selection
YASKAWA TOEP YAIP1W 02E YASKAWA AC Drive - iQpump1000 Installation & Start-up Guide
Setting Range
-999.9 to 999.9%
-999.9 to 999.9%
Setting Range
000 to 999
000 to 999
Setting Range
-999.9 to 999.9%
-999.9 to 999.9%
-999.9 to 999.9%
-999.9 to 999.9%
Refer to Terminal AM/FM Signal
Setting Range
0 to 2
0 to 2
Default
100.0%
0.0%
Default
102
103
Default
100.0%
0.0%
50.0%
0.0%
Default
0
0