i.4 Electrical Installation
n
Input Terminals
Table i.7
lists the input terminals on the drive. Text in parenthesis indicates the default setting for each multi-function input.
Type
No.
Multi-function input 1
S1
(Closed: Forward run, Open: Stop)
Multi-function input 2
S2
(Through mode)
Multi-function input 3
S3
(External pump fault, N.O.)
Multi-function input 4
S4
(Fault reset)
Multi-function input 5
S5
(Multi setpoint 1)
Multi-Function
Multi-function input 6
S6
Digital Inputs
(HAND mode)
Multi-function input 7
S7
(HAND mode 2)
Multi-function input 8
S8
(Through mode)
SC
Multi-function input common
SP
Digital input power supply +24 Vdc
Digital input power supply 0 V
SN
24 V transducer power supply 0 V
Multi-function pulse train input
RP
(Frequency reference)
+V
Power supply for analog inputs
24 V +24 Vdc transducer power supply for customer use 150 mA maximum capacity
Multi-function analog input 1
A1
Analog Inputs /
(Frequency reference bias)
Pulse Train
Input
Multi-function analog input 2
A2
(PID feedback)
Multi-function analog input 3
A3
(HAND frequency reference)
AC
Frequency reference common
E (G) Ground for shielded lines and option cards
n
Output Terminals
Table i.8
lists the output terminals on the drive. Text in parenthesis indicates the default setting for each multi-function output.
Type
No.
MA
N.O.
Fault Relay
MB
N.C. output
Output
MC
Fault output common
36
Table i.7 Control Circuit Input Terminals
Terminal Name (Function)
Table i.8 Control Circuit Output Terminals
Terminal Name (Function)
YASKAWA TOEP YAIP1W 02E YASKAWA AC Drive - iQpump1000 Installation & Start-up Guide
Function (Signal Level) Default Setting
• Photocoupler
• 24 Vdc, 8 mA
Refer to Sinking/Sourcing Mode for Digital Inputs on page
Multi-function input common
24 Vdc power supply for digital inputs, 150 mA max
NOTICE: Do not jumper or short terminals SP and SN. Failure to
comply will damage the drive.
• Input frequency range: 0 to 32 kHz
• Signal Duty Cycle: 30 to 70%
• High level: 3.5 to 13.2 Vdc, low level: 0.0 to 0.8 Vdc
• Input impedance: 3 kΩ
10.5 Vdc (max allowable current 20 mA)
• -10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
• 4 to 20 mA, 0 to 20 mA (input impedance: 250 Ω)
• Voltage or current input must be selected by jumper S1 and H3-01.
• -10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
• 4 to 20 mA, 0 to 20 mA (input impedance: 250 Ω)
• Voltage or current input must be selected by jumper S1 and H3-09.
• -10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
• 4 to 20 mA, 0 to 20 mA (input impedance: 250 Ω)
• Voltage or current input must be selected by jumper S1 and H3-05.
0 V
Function (Signal Level) Default Setting
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA
40.