Data Sets For Third-Party Battery Modules - Siemens SITOP PSU8600 Manual

Power supply system
Hide thumbs Also See for SITOP PSU8600:
Table of Contents

Advertisement

Engineering and remote access
7.6 Cyclic and acyclic data
Data
Operating Hours [h]
Battery temperature
[°C]
Fill byte(s)
7.6.2.7

Data sets for third-party battery modules

Index 1: General (reading/writing)
Data
Type
Operating Temperature [°C]
Capacity [Wh]
EndOfChargeVoltage [10mV]
MaxChargeCurrent [10mA]
TempCoefficient
StartOfPreserveVoltage [10mV]
EndOfDischargeVoltage [10mV]
268
Description
Total operating hours
Temperature of the battery module
-
5 = EndOfLife-
End of lifecycle has been
timeReached
reached.
6 = MaintenaceRe-
Maintenance required.
quired
7 = Change completed Battery module success-
fully replaced.
8 = Battery defective
Battery module defective
9 = Not ready for buff-
Battery module is not fully
ering
charged and is not ready
for buffering.
10 = Not completely
Battery module is not fully
loaded but ready for
charged, but is ready for
buffering
buffering.
11 = Ready for buffer-
Ready for buffering.
ing
12 = DeepDischarge-
Battery module was deep-
Recovery
discharged and is in the
recovery phase.
Description
Battery type
0
1
Operating temperature
Combined nominal capacity of the connected bat-
tery modules
Final charge voltage
Maximum charging current
Temperature coefficient
Start of the trickle charging voltage
End of the discharge voltage
Data type
Unsigned32
Signed8
Unsigned8
Data type
Pb
Unsigned8
pPb
Signed8
Unsigned16
Unsigned16
Unsigned16
Unsigned16
Unsigned16
Unsigned16
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76

Advertisement

Table of Contents
loading

Table of Contents