Siemens SITOP PSU8600 Manual page 320

Power supply system
Hide thumbs Also See for SITOP PSU8600:
Table of Contents

Advertisement

Engineering and remote access
7.8 OPC UA server
Display name
Alarm_MR_UnexpectedModuleDetected
Alarm_N_BufferDisabled
Alarm_N_ChargingDisabledByCommand Boolean
Alarm_N_RestartAfterSafetyShutdown
Alarm_N_SerialnumberDiverge
Alarm_N_SetpointParametersOutOf
Range
Alarm_N_SoftwareVersionDiverge
Alarm_N_SystemModeManual
Alarm_N_SystemStateStartup
Alarm_N_UCMBuffering
Alarm_N_UCMReady
Alarm_N_ClientShutdownFinished
Alarm_N_ClientShutdownInitiated
Alarm_MR_BufferingNotPossible
Alarm_MR_BufferingInsufficientCharging Boolean
Alarm_N_BufferingDisabledByCommand Boolean
Alarm_N_ChargingDisabledByCommand Boolean
Alarm_MR_InputOvervoltage
Alarm_MR_InputUndervoltage
Alarm_MD_ShutdownPrimary
Alarm_MD_SystemConfigReadError
Variables "ID" and "Severity" are assigned to each alarm.
320
Data type
Definition
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Sitop_8600_AlarmType
Sitop_8600_AlarmType
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Description
Unexpected module type detected.
Buffer deactivated.
Loading the buffer component(s)
using the control command deac-
tivated
The device has been restarted
after an automatic shutdown.
Different serial number detected.
A parameter value is outside its
maximum value (e.g. the S7 at-
tempts to set 28.8 V; however, the
module can only provide 28.0 V,
and therefore goes into limiting).
The alarm is displayed in conjunc-
tion with the alarm to replace the
module.
The device was switched to the
MANUAL mode. Control via the
PLC is now no longer possible.
Information that the system will be
started.
Buffer mode.
Ready for buffering.
Client run down.
System has initiated that the client
is run down.
Buffering not possible.
Module is not sufficiently charged
in order to be able to buffer.
Buffering remotely deactivated.
Charging remotely deactivated.
An overvoltage condition was de-
tected at the input.
Voltage at the input is too low.
The resonance converter of the
power supply was shut down.
The system configuration cannot
be read from the EEPROM.
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76