Siemens SITOP PSU8600 Manual page 232

Power supply system
Hide thumbs Also See for SITOP PSU8600:
Table of Contents

Advertisement

Engineering and remote access
7.6 Cyclic and acyclic data
Slot
Subslot Data
1-6
5
Channel4 Utarget
[10 mV]
Channel4 Ilimit
[10 mA]
Channel4 Ithreshold
Channel4
OutputEnable
Channel4 Reset_In
Data block active
6EP4436-8XB00-0DY0
Slot
Subslot Data
1-6
2
Channel1 Utarget
[10 mV]
Channel1 Ilimit
[10 mA]
Channel1 Ithreshold
Channel1
OutputEnable
Channel1 Reset_In
Data block active
1-6
3
Channel2 Utarget
[10 mV]
Channel2 Ilimit
[10 mA]
Channel2 Ithreshold
Channel2
OutputEnable
Channel2 Reset_In
Data block active
1-6
4
Channel3 Utarget
[10 mV]
232
Description
see data "Channel 1"
Description
Currently set setpoint of the output
voltage for output 1.
Response threshold of the output
current for output 1. When this is
exceeded, the output current is
interpreted as having an overload
condition and is shut down with a
time delay - or limited.
Prewarning threshold of the confi-
gured response threshold for the
output current in %. An alarm is
initiated when the actual output
current exceeds this value. Opera-
tion is continued without any re-
strictions. Prewarning is
deactivated by entering "0 %".
Switches output 1 on or off. A pos-
sible automatic shutdown due to
overload or power failure is not
taken into account.
Resets an overload shutdown for
this output
Indicator: Data block contains valid
data.
see data "Channel 1"
see data "Channel 1"
Value range
Data size
Value range
Data size
4.0 V - 28.0 V
Unsigned16
(default setting:
24.0 V)
Output 2.5 A:
Unsigned16
0.0 A - 2.5 A
(default setting: 2.5 A)
0 - 100 %
Unsigned8
(default setting: 90 %)
0 = false, >0 = true
Unsigned8
(default setting: false)
0 = false, >0 = true
Unsigned8
(default setting: false)
0 = false, >0 = true
Unsigned8
(default setting: false)
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76

Advertisement

Table of Contents
loading