2.8.5
Battery modules
No.
①
States of the LEDs
Table 2- 16
LED "O.K."
Signaling
Green
Flashing green (1/1)
Flashing green (0.25/0.25)
Flashing yellow (1/1)
Flashing yellow (0.25/0.25)
Red
Flashing red (1/1)
Flashing red (0.25/0.25)
Alternating, green/red
(0.25/0.25 A for 5 s)
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
Labeling
Signal type
O.K.
LED
①
Battery module fully charged
Battery module is being charged, buffer mode possible
Battery module being charged, charge state insufficient for buffer operation
Battery module temperature is outside the permissible range
•
Interrupted communication cable
•
Restricted charge operation, buffer operation is possible
The end of the battery service life has been reached (according to EUROBAT
80% of the rated capacity), it is recommended that the batteries are replaced
Buffer mode is still possible
Cyclic battery test is negative, batteries must be replaced
Buffer mode not possible
Restoration mode after deep discharge, charge state insufficient for buffer opera-
tion
Battery module connected with incorrect polarity, buffer mode not possible
•
Power connections interrupted or fuse defective/ruptured, buffer mode not
•
possible
While replacing the battery, request to immediately reset the lifetime counter
•
using the reset button
Battery replacement confirmed
Description, device design, dimension drawing
Signaling
Device status
2.8 Display elements
57