Installation
6.1 Line-side connection
Protection
Protection 6EP3436-8MB00-2CY0
Protection
required
Protection 6EP3437-8MB00-2CY0
Protection
required
The protective conductor of the line supply must be connected at the "PE" terminal.
Additional information is provided in Chapter "Connections and terminal designations
(Page 32)".
154
3-pole coupled miniature circuit breaker (IEC 898) characteristic C, 6 - 16 A
or
3RV2011-1DA10 circuit breaker, setting of the thermal overcurrent release: 3 A
or
3RV2711-1DD10 circuit breaker (branch circuit protection acc. to UL489-listed,
DIVQ)
3-pole coupled miniature circuit breaker (IEC 898) characteristic C, 10 - 16 A
or
3RV2011-1DA10 circuit breaker, setting of the thermal overcurrent release: 3 A
or
3RV2711-1DD10 circuit breaker (branch circuit protection acc. to UL489-listed,
DIVQ)
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76