Troubleshooting
8.3 Alarm list web server
ID
Severity
74
N
75
N
76
N
77
N
78
N
Alarm list SITOP BAT8600
The IDs for the BAT8600 module alarms depend on the number of the particular battery
module:
● Battery 1: 100 + ID
● Battery 2: 130 + ID
● Battery 3: 160 + ID
● Battery 4: 190 + ID
● Battery 5: 220 + ID
ID
Severity
1
MD
2
MR
3
MR
4
MD
5
MR
6
MR
7
N
8
N
10
MR
11
MD
12
MD
13
MD
14
MR
380
Event
Battery capacity tracing test can-
celed. Battery not fully charged
Battery capacity tracing test can-
celed. Insufficient system load
Battery capacity tracing test can-
celed by user
Battery capacity tracing test can-
celed. Buffering started
Battery capacity tracing test can-
celed. Input voltage too high
Event
Incompatible battery detected
New battery detected
Unknown battery
Module with reduced power de-
tected.
Module with excessive power de-
tected.
Unexpected module type detected.
Different serial number detected
Different firmware version detected Different firmware version detected
Deep discharge battery
Battery defective
Fuse is defective (battery index:
{1:d})
Battery temperature high, battery
switched off
Warning before battery over-
temperature
Help text
The battery capacity tracing test can not be started because
of not fully charged batteries.
The battery capacity tracing test is canceled because of
insufficient system load.
The battery capacity tracing test is canceled by the user.
The battery capacity tracing test is canceled because of
started buffering mode.
The battery capacity tracing test is canceled because of too
high input voltage.
Help text
The battery is a type that is not compatible with the configu-
ration. The battery cannot be commissioned.
New battery detected
Data cannot be read correctly from the battery. Battery is
defective or not supported by SIEMENS.
A module with reduced power was detected. Deviating sys-
tem behavior may be possible.
A module with excessive power was detected. Normal oper-
ation of the system is possible.
Unexpected module type detected.
Different serial number detected
Battery is deep discharged - no buffering possible.
Battery defective - neither buffer nor charging operation is
possible
Fuse is defective.
The temperature of the battery is too high. The battery was
switched off for safety reasons. Buffering is no longer possi-
ble depending on the number of connected batteries!
Battery temperature too high – battery service life is short-
ened
Power supply system SITOP PSU8600