● Dead time for system output current prewarning
An alarm for the prewarning threshold for the total current is only initiated if a continuous
system overload occurs, which is longer than the set dead time.
● General prewarning threshold for individual output current in MANUAL mode
Here, it is possible to define a common threshold value for all outputs, above which an
alarm is output.
Enter a value of "0 %" to deactivate the prewarning threshold.
● Dead time for alarm message 'Input voltage outside permitted range'
A buffer mode alarm is only initiated if the power continuously fails for a time that is
longer than the set dead time.
Buffering parameters
Parameter
Buffer component disabled via control
command
Enable LONGLIFE operating mode
Threshold value for sufficient buffer readi-
ness
Preferred UPS module when the line sup-
ply fails
Preferred charging mode for a system
start
Enable short-time interruption at output 1
Time X: Dead time up to the beginning of
short time interruption
Time A: Wait time until the short-time
interruption
Time B: Duration of short time interruption
Time C: Waiting time after shutdown com-
pleted
Define that only output 1 is activated when
starting from a battery module.
Examples for conversion
ms (milliseconds)
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
Value range
Yes/no
Yes/no
10 - 90 %
Alternating discharge
UPS8600[1]
UPS8600[2]
Yes/no
Yes/no
0 - 3 600 000 000 ms
0 - 3 600 000 000 ms
0 - 3 600 000 000 ms
0 - 3 600 000 000 ms
Yes/no
s (seconds)
3 000
5 000
15 000
60 000
300 000
Engineering and remote access
7.5 SIMATIC STEP 7
Default setting
No
No
85 %
Alternating discharge
No
No
3 000 ms
15 000 ms
5 000 ms
3 000 ms
No
m (minutes)
3
5
15
60
300
¼
1
5
215