Display name
Alarm_MR_BatteryPackDefect
Alarm_MR_BatteryParameters
Corrupt
Alarm_MR_BatteryPowerlineDis-
connected
Alarm_MR_BatteryTemperature
HighError
Alarm_MR_BatteryTemperature
HighWarning
Alarm_MR_BatteryTemperature
LowError
Alarm_MR_BatteryTemperature
LowWarning
Alarm_MR_FuseBlown
Alarm_MR_MoreCapableBattery
Detected
Alarm_MR_NewBatteryDetected
Alarm_MR_UnexpectedBatteryDe-
tected
Alarm_MR_UnknownBatteryDe-
tected
Alarm_N_BatteryLifetimeCounter
Reseted
Alarm_N_EndOfServiceLifeWar-
ning
Alarm_N_SerialnumberDiverge
Alarm_N_SoftwareVersionDiverge
ParameterSet
/
All variables of the SITOP UPS8600 battery module are listed together under the
"ParameterSet" node.
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
Data type
Definition
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Engineering and remote access
7.8 OPC UA server
Description
The battery voltage inside the
module exhibits an abnormal de-
viation and should be replaced in
order to avoid buffering problems.
The battery configuration is corrupt.
The battery behavior remains un-
changed, however.
Connection to battery interrupted -
check connection and fuse
Battery temperature is too high and
the battery was shut down for safe-
ty reasons. Buffering is no longer
possible depending on the number
of connected batteries.
Battery temperature too high –
battery life will be shortened
The battery temperature is too low.
The battery will not operate in this
situation. Buffering is no longer
possible depending on the number
of connected batteries.
Battery temperature too low - re-
duced output current
Fuse is defective
A module with excessive power
was detected. Normal operation of
the system is possible.
New battery detected
Unexpected module type detected.
Unexpected module type detected.
After the battery was successfully
replaced, the determination of the
battery lifetime was reset and then
restarted.
It is recommended to replace the
battery because the battery lifetime
has reached its calculated end and
restricted buffer readiness is prob-
able.
Different serial number detected
Different firmware version detected