Siemens SITOP PSU8600 Manual page 319

Power supply system
Hide thumbs Also See for SITOP PSU8600:
Table of Contents

Advertisement

Display name
Alarm_MD_Systemoverload
Alarm_MD_SystemConfigReadError
Alarm_MD_SystemParametersCorrupt
Alarm_MR_ModuleParametersCorrupt
Alarm_MR_MoreCapableModuleDetec-
ted
Alarm_MR_NewModuleDetected
Alarm_MR_Output1InterruptionShutdow
nInitiated
Alarm_MR_ShutdownPrimary
Alarm_MR_Systemoverload
Alarm_MR_SystemoverloadPeakLoad
Alarm_MR_SystemParametersCorrupt
Alarm_MR_SystemShutdown
Alarm_MR_SystemStateBuffering
Alarm_MR_SystemStateCooledDown
Alarm_MR_SystemStateReadyForRe-
start
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
Data type
Definition
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Boolean
Sitop_8600_AlarmType
Engineering and remote access
7.8 OPC UA server
Description
The system load lies about the
nominal maximum value, but still
within the defined overload profile.
The device is still functioning com-
pletely and normally.
The system configuration cannot
be read out of the EEProm.
The stored system configuration is
incorrect/corrupt. Deviations from
the expected response can occur if
the device is not operated under
normal conditions.
The stored module configuration is
incorrect/corrupt. The device con-
tinues to operate consistently.
Module with excessive power de-
tected.
A new module has been found that
has still not been configured.
Shutdown of output 1 is initiated.
The resonance converter of the
power supply is shut down.
The system load is above the set
system load alarm threshold.
The system load is outside the
defined overload profile (either
because of the magnitude or be-
cause the time was excessively
long). The outputs of the channel
expansions are shut down.
The system configuration is defec-
tive/false. The system can be op-
erated.
General error. The device is still
functioning as configured and as
expected.
Buffer mode.
After a system overload / after a
short-circuit, the device has cooled
down again, and can be reactivat-
ed after switching off the supply
and switching on again.
System can be switched on again
after automatic shutdown due to
impermissible operating condition.
To reactivate the system, it must
be switched-off and switched-on
again - or it must be restarted using
a remote reset.
319