Battery; Power Supply Load Calculation Table - Siemens BC8001A Installation And Operating Instruction

Table of Contents

Advertisement

5.

Battery

Wiring as refer to figure 6.
Maximum battery circuit
current
Capacity
Expected battery standby
operational times
Dimension(mm)
Battery Maintenance
Check battery regularly, if the following things happen, eg.
function is not normal, housing is distorted, liquid releases,
the battery must be changed. If the battery is dirty, please
use towel with warm water to clean it. Do not use petrol, or
chemical liquid.
To be stored at -10℃ ~ +50℃ temperature and dry place.
To be stored at full chargeable status. To be charged before being used because of self discharge.
6.

Power supply load calculation table

No
Type
Description
.
1.
BDS031A
Addressable heat detector
2.
BDS051A
Addressable smoke detector
3.
BDS121A
Manual signaling box
4.
BCC8001A
Main Board+CPU
5.
BDS132A
Input Module
6.
BDS221A
Output Module
7.
NAC
8.
U-MCS
Multicandela selectable strobe(red)
9.
U-MMT-MCS
Multitone horn Strobe(red)
10.
DSC
Dual sync control module
11.
P2475
SpectrAlert horn/strobe
12.
MDL
Sync-Circuit module
BC8001A Installation and Operating Instruction
Charging: 3.1A
Discharging:6A
Sealed Leaded
Acid,12VDC,12Ah×2
24 Hours and 5 Minutes alarm
181×76×167(L×W×H)
Power Supply
-
Battery
Figure 6
Battery and AC power connection diagram
Quantity
Quiescent
current(mA)
0.8
0.8
0.8
90.0
1.0
1.0
0
0
0
0
0
0
Total System Current
Bat- Bat+
+
-
Battery
Max.
Total Quiescent
current(mA)
current(mA)
1.0
1.0
1.0
130.0
3.0
3.0
1500.0
145.0
200.0
55.0
245.0
12.0
Page 12/49
+