Output Data - Siemens SITOP PSU8600 Manual

Power supply system
Hide thumbs Also See for SITOP PSU8600:
Table of Contents

Advertisement

9.2

Output data

Basic units
Output
Number of outputs
Rated output voltage U
out rated
(factory setting)
Total tolerance, static ±
Static line regulation, approx.
Static load regulation, approx.
Residual ripple in the load range
peak-peak, max.
Spikes peak-peak, max.
(bandwidth, approx. 20 MHz)
Adjustment range
Comment
Output voltage adjustment
Operating display
Signaling
Switch-on/switch-off behavior
Starting delay, max.
Rise time of the output voltage, max.
Switching on outputs
Rated output current I
out rated
Current range
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
Basic unit
6EP3436-8SB00-2AY0
Regulated, isolated DC voltage
1
1)
DC
24 V
3 %
0.2 %
0.1 %
100 mV
200 mV
4 - 28 V
Derating > 24 V: 4 % I
Via potentiometer
or in the REMOTE operating mode
3-color LED for the device operating
status;
LED for MANUAL / REMOTE mode;
4 LEDs for PROFINET communication;
3-color LED for the device operating
status;
Relay contact (changeover contact,
rating 60 V DC /0.3 A) for "O.K."
No overshoot of U
1 s
500 ms
In conjunction with CNX8600 expansion module: all outputs are simultaneously
switched-on after the device powers up, after a delay time of 25 ms, 100 ms – or
"load optimized" where the outputs are sequentially switched-on, can be selected
via DIP switch
20 A
0 - 20 A
50 ... 60 °C:
Derating 2.5 %/K
Basic unit
6EP3437-8SB00-2AY0
1
1)
24 V
3 %
0.2 %
0.1 %
100 mV
200 mV
4 - 28 V
/V
Derating > 24 V: 4 % I
out
Via potentiometer
or in the REMOTE operating mode
3-color LED for the device operating
status;
LED for MANUAL / REMOTE mode;
4 LEDs for PROFINET communication;
3-color LED for the device operating
status;
Relay contact (changeover contact,
rating 60 V DC /0.3 A) for "O.K."
(Soft-Start)
out
1 s
500 ms
40 A
0 - 40 A
50 ... 60 °C:
Derating 2.5 %/K
Technical data
9.2 Output data