257
39
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
Severity
Alarm text
MR
Buffer mode
N
Device starting up.
N
Device is in manual mode.
F
Expansion module is not avai-
lable.
F
Invalid number of modules.
MR
New unconfigured module
detected.
F
Invalid system configuration.
MD
Stored system configuration is
corrupt.
MR
Invalid system configuration.
F
Hardware failure
MR
Module with excessive power
detected.
MR
Unexpected module type de-
tected.
MD
Module with reduced power
detected.
F
Incompatible module detected.
F
Unexpected empty slot detect-
ed.
N
Buffer mode
N
Sufficient buffer readiness
N
Buffer readiness disabled
F
Unknown module found (slot 1). Unknown module found (slot 1).
F
Unknown module found (slot 2). Unknown module found (slot 2).
F
Unknown module found (slot 3). Unknown module found (slot 3).
F
Unknown module found (slot 4). Unknown module found (slot 4).
F
Unknown module found (slot 5). Unknown module found (slot 5).
F
Unknown module found (slot 6). Unknown module found (slot 6).
F
Unknown module found.
Help text
The power supply system is supplied via the buffer
expansion module(s).
Device starting up.
The device was switched to manual mode. Remote
configuration and control are not possible.
Expansion module was not found. Power supply
system response deviates from the configuration.
Invalid number of modules detected. Invalid slot.
New unconfigured module detected.
System configuration is incorrect. Normal operation
of the system is not possible.
Stored system configuration is corrupt. Deviations
from the expected response may occur outside nor-
mal operation.
System configuration is different. The system can be
operated.
A hardware failure has occurred. All outputs of the
power supply system have been switched off.
A module with excessive power was detected. Nor-
mal operation of the system is possible.
Unexpected module type detected.
A module with reduced power was detected. Deviat-
ing system behavior may be possible.
The module has a module type that is incompatible
with the configuration. The module cannot be com-
missioned.
Unexpected empty slot detected.
The primary power supply has failed; the power sup-
ply system is being supplied through the buffer com-
ponent.
Sufficient buffer readiness has been achieved; the
charge status of the buffer components in the system
has reached the preset threshold value.
No buffering possible because the buffer component
has been disabled.
Unknown module found.
Troubleshooting
8.2 PROFINET alarm list