Buffer components, maximum number and compatibility
A maximum of two buffer components can be used with a basic unit. Maintenance-free buffer
modules with integrated energy-storage device (electrolytic capacitors, double-layer
capacitors) are available as buffer components to buffer shorter power failures. There is also
a UPS module and battery modules (with lead or lithium iron phosphate batteries) as
external energy storage device to buffer longer power failures.
Buffer modules, PSU8600 power supply system
Type
SITOP BUF8600 100 ms/40 A
SITOP BUF8600 300 ms/40 A
SITOP BUF8600 4 s/40 A
SITOP BUF8600 10 s/40 A
Note
It is possible to use different buffer modules in one system. This means that a buffer time of
400 ms (100 ms + 300 ms) can be realized, for example.
UPS module, power supply system PSU8600
Type
SITOP UPS8600 960 W
Up to 5 battery modules of the same type can be connected in parallel to a UPS module.
Battery modules, PSU8600 power supply system
Type
SITOP BAT8600 LiFePO4 264 Wh
SITOP BAT8600 Pb 380 Wh
"Pb" battery modules from third-party suppliers can be connected.
Note
Using SITOP BUF8600 and SITOP UPS8600 in one system
If a buffer module and a UPS module are used in a system, then the buffer module is first
charged, and in the buffer mode is the first to be discharged. After the buffer module has
been discharged, then the UPS module takes over the buffering. In the buffer mode, the
UPS module does not charge the buffer module that has already been discharged.
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
Mounting and maintenance
4.3 Permissible hardware configurations
Article number
6EP4297-8HB00-0XY0
6EP4297-8HB10-0XY0
6EP4293-8HB00-0XY0
6EP4295-8HB00-0XY0
Article number
6EP4197-8AB00-0XY0
Article number
6EP4143-8JB00-0XY0
6EP4145-8GB00-0XY0
123