Description, device design, dimension drawing
2.8 Display elements
States of the individual LEDs
Table 2- 6
LED "O.K."
Signaling
Off
Green
Flashing green (1/1)
Flashing green (0.25/0.25)
Red
Flashing red (0.25/0.25)
Yellow
Flashing yellow (0.25/0.25)
Alternating, green/red
(0.25/0.25)
Table 2- 7
LED "MAN"
Signaling
Off
Green
Flashing green (1/1)
46
Device is OFF or is powering up (booting)
Normal operation
Phase asymmetry or phase failure
Detection from:
approx. 50 % rated load for 6EP3437-8MB00-2CY0
approx. 75 % rated load for 6EP3436-8MB00-2CY0
Operation with rated load is permissible for approx. 10 min.
System overload in normal operation:
Total output power in the range 101 - 150 %
Operation is permissible for 5 s/min
ERROR OFF: Device has automatically shut down as a result of device over-
temperature, phase dissymmetry, system overload
Internal device fault
Device ready for the automatic ERROR OFF shutdown to be reset – or after
a firmware update has been completed, by switching off the supply voltage
and switching it on again (power OFF/ON)
Incorrect hardware configuration (REMOTE operating mode)
Power failure, buffer operation active
System overload in buffer operation: Total output power in the range 101 - 150 %
Operation is permissible for 5 s/min
Firmware being updated
Device is OFF or is powering up (booting)
REMOTE mode, i.e. parameterization and remote control via PROFINET or
web server
MANUAL mode, i.e. setting directly at the device
MANUAL mode; the mode has been changed in operation, settings directly at
the device do not necessarily correspond to the active reference parameters.
Power supply system SITOP PSU8600