Index 48: PROFIenergy values (reading/writing)
Data
PROFIenergyEnabled (0/255)
Fill byte(s)
TimeToPause [ms]
TimeToOperate [ms]
MinimumStay [ms]
MaximumStay [ms]
SavingPowerConsumption [kW]
OperatePowerConsumption [kW]
EnergyConsumptionToPause [kWh]
EnergyConsumptionToOperate [kWh]
Index 49: PROFIenergy channel list (reading/writing)
Data
ChannelsOffList
Index 53: Web server (reading/writing)
Data
WebserverEnabled
AutoReloadEnabled
ReloadTime
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
Description
Enable PROFIenergy on this device
-
Time that elapses up to the start of PROFIenergy
pause
Time that elapses up to the start of operation
Minimum dwell time [s]
Maximum dwell time [s]
Power consumption in the energy-saving mode
[kW]
Power consumption in operation [kWh]
Power drawn up to the start of the pause [kWh]
Power drawn up to the start of operation [kWh]
Description
Overview of the outputs that are switched off. Each
output is represented using 1 bit (starting with bit 0
for output 1).
Description
Activating/deactivating the web server of the
SITOP PSU8600:
0: disable
•
255: enable
•
Enable/disable automatic update:
0: disable
•
255: enable
•
Update interval:
0: Off
•
5: 5s
•
10: 10s
•
20: 20s
•
30: 30s
•
60: 60s
•
Engineering and remote access
7.6 Cyclic and acyclic data
Data type
Unsigned8
3xUnsigned8
Unsigned32
Unsigned32
Unsigned32
Unsigned32
Float
Float
Float
Float
Data type
Unsigned64
Data type
Unsigned8
Unsigned8
Unsigned8