Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
Severity
Alarm text
N
The actual value of the output
current is above the set ad-
vance warning threshold.
MR
Output is ready to be switched
on.
N
Current limit on the output after
occurrence of an overload.
N
Output 1 was switched off
manually.
N
Output switched off during
buffering
N
Output was switched off.
N
Output was switched on.
N
Parameter out of permissible
value range.
F
Safety shutdown of the output
F
Output has been shut down
because of a class 2 exception.
MR
Buffer mode.
MR
Not ready for buffering
N
Ready for buffering.
N
Limited buffer capacity.
F
Shutdown due to overtempera-
ture.
MD
Prewarning overtemperature.
MR
Output 1 interruption: Shutdown
initiated
N
Not ready for buffering
MD
Battery not available
MD
Wrong battery polarity
MR
Surplus battery
MR
Buffering mode not possible
due to low charge
Help text
The actual value of the output current is above the
configured advance warning threshold and is below
the response threshold.
Output is ready to be switched on again after auto-
matic overload shutdown.
Output is in overload mode. The output current is
limited to the configured response threshold.
Output was switched off manually directly on the
device.
Output switched off during buffering
Output was switched off.
Output was switched on.
A control command is attempting to set a value out-
side the value range that the hardware module can
implement. The value is automatically limited to the
minimum or maximum permitted value for the mo-
dule.
A critical fault has occurred. The output was switched
off by the power supply system.
Output has been shut down because of a class 2
exception.
The power supply system is supplied via the buffer
expansion module(s).
Not ready for buffering. Energy storage voltage is too low.
Ready for buffering. Energy storage fully charged.
Limited buffer capacity. Energy storage is not fully
charged.
Shutdown due to overtemperature. Buffer component
disabled.
Danger of overtemperature detected in a system
component. Immediate load reduction is recom-
mended.
The shutdown of output 1 has been initiated in the
course of the output 1 interruption sequence.
The energy storage is not charged sufficiently for
buffering.
Attempting to access a battery that is not available.
Either the battery with the requested number was
never connected or communication with this battery
was interrupted.
Wrong battery polarity - check battery connections.
More than 6 batteries are connected. Connect a
maximum of 6 batteries to the Energy Storage Link.
Buffer mode is not possible - check settings, cabling,
fuse, and battery voltages
Troubleshooting
8.2 PROFINET alarm list
361