Engineering and remote access
7.8 OPC UA server
SubDevices
The parameters for the battery modules are listed under the "SubDevices" nodes.
SITOP BAT8600 battery modules
ActualState
Display name
ModuleOperatingState
ModuleStateOfHealth
ModuleCapacity
ModuleTemperature
ModuleOperatingHours
ModuleStateLed
Alarm
Display name
Alarm_MR_BatteryCommunication
Disconnected
Alarm_MD_BatteryDefect
Alarm_MD_BatteryParameters
Corrupt
Alarm_MD_BatteryTemperature
HighError
Alarm_MD_BatteryTemperature
LowError
Alarm_MD_IncompatibleBatteryDe-
tected
Alarm_MD_LessCapableBattery
Detected
Alarm_MR_BatteryDeepDischarge
342
Data type
Definition
Enumeration
MultiStateDiscrete-
Type
Integer
AnalogItemType
Integer
AnalogItemType
Integer
AnalogItemType
Integer
AnalogItemType
Object
Sitop_8600_LedType
Data type
Definition
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Description
Battery status
State of health of the battery mo-
dule
Capacity of the battery module
Battery temperature
Total operating time of the batteries
Actual state of the LED display
"O.K."
Description
Communication to the battery is
interrupted. Buffering is still possi-
ble, the battery charge level has
been reduced to a minimum how-
ever.
Battery defective - neither buffer
nor charging operation is possible
The battery configuration is corrupt.
Battery behavior may deviate.
Battery temperature is too high and
the battery was shut down for safe-
ty reasons. Buffering is no longer
possible depending on the number
of connected batteries.
The battery temperature is too low.
The battery will not operate in this
situation. Buffering is no longer
possible depending on the number
of connected batteries.
The battery is a type that is not
compatible with the configuration.
The battery cannot be commis-
sioned.
A module with reduced power was
detected. Deviating system beha-
vior may be possible.
Battery is deep discharged - no
buffering possible.