Engineering and remote access
7.6 Cyclic and acyclic data
Operating state, output 1 ... n (channel1 ... n operating state)
The status messages of an output are listed in the table below. The data applies to outputs 1
to n.
Status message
0 = ManualOff
1 = RemoteOff
2 = BufferOff
3 = OverLoadOff
4 = ReadyForRestart
5 = ErrorOff
6 = Boot
7 = Running
8 = OverLoad
9 = Limit
10 = OverloadWithDerating
11 = LimitWithDerating
12 = Locked
7.6.1.5

Operating states SITOP BUF8600

Operating state of the buffer module (buffer operating state)
Status message
0 = Off
1 = Boot
2 = Full
3 = Buffering
4 = ErrorOff
5 = ReadyForRestart
6 = NotFully
ChargedReady
7 = NotFully
ChargedNotReady
8 = Disable
9 = FwUpdate
10 = BufferEnd
236
Description
Output switched off manually (button): The output was manually switched off using the
button on the device. The device can only be switched on manually using the button on the
device.
Output switched off (PROFINET/IE): The output was remotely switched off via
PROFINET/IE.
Output switched off (prioritization output 1): The output was switched off during buffering.
Output switched off (overload): Invalid overload occurred at the output. The output was
switched off.
Output ready for reset (reset): Output is ready to be switched on again after automatic over-
load shutdown.
Output switched off (error)
Output switched off (startup)
Output switched on (normal operation)
Output in overload operation: The output current is above the specified response threshold,
but still within the permissible overload profile.
Output current limited to the response threshold: The output is in the overload mode. The
output current is limited to the configured response threshold.
Output in overload operation (system overload)
Output current limited (system overload)
Output switched off as the UPS8600 is being charged
Description
Buffer component is in the "Off" operating state.
Buffer component is powering up.
Complete buffer readiness: The energy storage device of the buffer component is fully
charged (normal operation).
The buffer component is operating in the buffer mode: The power supply system is supplied
via the buffer component(s).
Shutdown after error: A fault/error has occurred when operating the buffer component. The
buffer component is not operational and must be restarted by switching off the supply volt-
age and switching it on again.
Ready for a new start
Ready for buffer operation as the energy storage device of the buffer component has been
sufficiently charged, but has not been fully charged.
Not ready for buffering as the energy storage device of the buffer module has not been
sufficiently charged and is presently being charged.
Buffer component is deactivated.
Firmware is being updated
Buffering ended
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76