Engineering and remote access
7.5 SIMATIC STEP 7
Note
Response for a PROFIenergy pause:
As soon as the command to start a PROFIenergy pause is issued via PROFINET, the
operating status of the outputs cannot be influenced using switch-on or shutdown
commands, which are sent in the REMOTE operating mode during the PROFIenergy pause.
These commands are buffered up to the end of the PROFIenergy pause.
The configuration of the outputs is automatically updated as soon as the command to exit
the PROFIenergy pause is issued. All of the switch-on and shutdown commands that
occurred during the PROFIenergy pause are taken into account.
All other commands are immediately executed, even during a PROFIenergy pause.
PROFIenergy output parameters
The outputs are selected using a binary number, which is converted into a decimal value.
Example
Binary number 1111101001 is converted into decimal value 1001.
Parameter
Outputs that can be switched off for a
PROFIenergy pause
*maximum value for 33 outputs
Web server
Parameter
Activate web server on this module
Enable automatic update
Automatic update
Update interval
Enable automatic logoff
Permit access only with HTTPS
218
Value range
0 ... 8.589.934.591
(0x1 FFFF FFFF)*
Value range
Yes/no
Yes/no
0 / 5 s / 10 s / 20 s / 30 s / 60 s
Yes/no
Yes/no
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
Default setting
0
Default setting
No
No
10 s
No
Yes