El9222-Xxxx - Beckhoff EL922 Series Documentation

Electronic overcurrent protection terminals
Table of Contents

Advertisement

7.6.2

EL9222-xxxx

7.6.2.1
Restore object
Index 1011 Restore default parameters
Index
Name
(hex)
1011:0
Restore default parame-
ters
1011:01
SubIndex 001
7.6.2.2
Configuration data
Index 80n0 Settings (for n = 0, Ch.1; n=1, Ch. 2)
Index (hex) Name
80n0:0
Settings
80n0:11
Nominal current
80n0:19
Switch Programming
Control
Index 80n0 DIG Safe State Active Ch.n
(n=2 for Ch.1; n=3 for Ch.2
Index
Name
(hex)
80n0:0
DIG Safe State
Active
80n0:01
Active
Index 80n1 DIG Safe State Value Ch.n
(n=2 for Ch.1; n=3 for Ch.2
Index
Name
(hex)
80n1:0
DIG Safe State
Value
80n1:01
Value
EL922x
Meaning
Restore default parameters
If this object is set to "0x64616F6C" in the set value dia-
log, all backup objects are reset to their delivery state.
Meaning
Max. Subindex
Nominal current (set fuse value), I
LED button programming option: Indicated whether
the nominal current of programmable terminals can
be programmed via the LED button.
Disable: Locked and not allowed. Only one query of
the nominal current is possible!
Enable: Programming possible
Meaning
Maximum subindex
Enabling of the output state defined in
index 0x80n1:01 in case of a bus error
0: output retains its current state.
1: output is switched to the state defined in
index 0x80n1.
Meaning
Maximum subindex
Defines the state of the output in case of a
bus error:
0: output off
1: output on
Version: 1.0
Data type
UINT8
UINT32
Data type
UINT8
UINT8
N
UINT8
Data type Flags Default value
UINT8
BOOLEAN RW
Data type Flags Default value
UINT8
BOOLEAN RW
Commissioning
Flags Default
RO
0x01 (1
)
dec
RW
0x00000000 (0
)
dec
Flags
Default
RO
0x19 (25
)
dec
RW
(0x80nF:17)
RW
---
RO
0x01 (1
)
dec
0x01 (1
)
dec
RO
0x01 (1
)
dec
0x00 (0
)
dec
123

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents