Beckhoff EL922 Series Documentation page 50

Electronic overcurrent protection terminals
Table of Contents

Advertisement

Mounting and wiring
The EL9227-xxxx has illuminated push-buttons!
The illuminated push-buttons allow the overcurrent protection terminal to be operated, e.g. switch-
ing on and off and resetting the respective output. They are also used for programming and query-
ing the nominal current. There are 3 modes: operation mode, programming mode and query mode.
There is a common programming mode in which the two outputs can be set simultaneously, as they
are interdependent for the terminal with sum current limitation.
Overview of the 3 operation modes:
Operation mode
The operation mode is active as soon as the overcurrent protection terminal is supplied with supply voltage,
the initialization has been successfully completed and no other mode is active. This is effectively the normal
mode of operation.
Programming mode
The programming mode is available for the adjustable overcurrent protection terminals. To enter this mode,
press and hold one of the two buttons in operation mode for > 3 seconds. In programming mode, both
outputs can be set simultaneously.
Query mode
The query mode exists for the fixed overcurrent protection terminals, which are not adjustable. If
programming is disabled for the adjustable overcurrent protection terminals, only the query mode is
available. No changes can be made in query mode, i.e. it is only intended for querying the nominal current
value. To enter this mode, press and hold one of the two buttons in operation mode for > 3 seconds.
For operation in the respective modes, please refer to the table LED buttons Operation / Programming.
Button LED Operation / Programming
LED
State
Operation in operation mode
Button LED 1
Press briefly
Long press (>3s)
Button LED 2
Press briefly
Long press (>3s)
Operation in programming mode
Button LED 1
Press briefly
Long press (>3s)
Button LED 2
Press briefly
Long press (>3s)
Press button LEDs 1 and 2 simultaneously for > 5 s
No operation for 45 seconds
Operation in query mode
Button LED 1
Press briefly
Long press (>3s)
Button LED 2
Press briefly
Long press (>3s)
No operation for 45 seconds
Sample programming
Further sample programming can be found in chapter "Sample programming [} 52]".
50
Meaning
Switching output 1 on and off or resetting it
Activating the programming or query mode
Switching output 2 on and off or resetting it
Activating the programming or query mode
Set nominal current value of output 1, press 1x = 1 A, press 2x = 2 A etc. up to
press 10x = 10 A, press more than 11x= OFF
For variants up to 4 A, press more than 5x = OFF applies
Saving the nominal current value and leaving the programming mode
Set nominal current value of output 2, press 1x = 1 A, press 2x = 2 A etc. up to
press 10x = 10 A, press more than 11x= OFF
For variants up to 4 A, press more than 5x = OFF applies
Saving the nominal current value and leaving the programming mode
Resetting to factory settings
After 45 seconds, the programming mode is automatically exited without saving
the settings.
No function
Exiting the query mode
No function
Exiting the query mode
After 45 seconds, the settings query mode is automatically exited again