Meaning of the EL9222-xxxx LEDs and button LEDs
LED
Color
Meaning
Button
Button LED 1 indicates the status of output 1.
LED 1
Green
off
on
flashing
flickering
Orange
on
Flash (after
pressing)
flashing
Red
on
flashing
Run LED Run LED indicates the EtherCAT operating state of the terminal
Green
off
flashing
Single flash
on
flickering
Ready
Ready LED indicates the status for overcurrent protection / programming mode / query mode
LED
Green
on
Orange
on
Red
on
flashing
flickering
Button
Button LED 2 indicates the status of output 2.
LED 2
Green
off
on
flashing
flickering
Orange
on
Flash (after
pressing)
flashing
Red
on
flashing
EL922x
Output 1 switched off
Output 1 switched on
Programming mode active:
Permissible nominal current value for output 1 can be read with flashing code (1x flashing =
1 A; 2x flashing = 2 A, etc.).
Switch-off process not yet completed,
wiring error: voltage detected at switched-off output ( with Ready LED green)
Output 1 switched on + prewarning threshold reached
Output 1 disabled (nominal current value is set to "OFF")
Reverse current active
or
Query mode or programming mode active (additionally orange Ready LED is on):
Nominal current value cannot be changed because disabled or fixed variant; set nominal cur-
rent value for output 1 can be read with flashing code (1x flashing = 1 A; 2x flashing = 2 A;
etc.)
Output 1 triggered
Output 1 triggered and cooling phase active
or
Programming mode active (additionally Ready LED orange on):
Sum current of both outputs exceeded, impermissible nominal current value for output 1 can
be read with flashing code (1x flashing = 1 A; 2x flashing = 2 A, etc.)
State of the EtherCAT State Machine [} 94]: INIT = initialization of the terminal
State of the EtherCAT State Machine: PREOP = function for mailbox communication and dif-
ferent default settings set
State of the EtherCAT State Machine: SAFEOP = verification of the Sync Manager [} 96]
channels and the distributed clocks.
The outputs remain in safe state.
State of the EtherCAT State Machine: OP = normal operating state; mailbox and process
data communication is possible
State of the EtherCAT State Machine: BOOTSTRAP = function for terminal firmware updates
[} 154]
24 V DC supply voltage present and initialization completed, overcurrent protection active,
operation mode active
Programming mode / query mode active
Missing 24 V DC supply voltage or initialization error
Loading the factory settings
Wiring error or cable break (e.g. wrong ground reference)
Output 2 switched off
Output 2 switched on
Programming mode active:
Permissible nominal current value for output 2 can be read with flashing code (1x flashing =
1 A; 2x flashing = 2 A, etc.).
Switch-off process not yet completed,
wiring error: voltage detected at switched-off output ( with Ready LED green)
Output 2 switched on + prewarning threshold reached
Output 2 disabled (nominal current value is set to "OFF")
Reverse current active
or
Query mode or programming mode active (additionally orange Ready LED is on):
Nominal current value cannot be changed because disabled or fixed variant; set nominal cur-
rent value for output 2 can be read with flashing code (1x flashing = 1 A; 2x flashing = 2 A;
etc.).
Output 2 triggered
Output 2 triggered and cooling phase active
or
Programming mode active (additionally Ready LED orange on):
Sum current of both outputs exceeded, impermissible nominal current value for output 2 can
be read with flashing code (1x flashing = 1 A; 2x flashing = 2 A, etc.)
Version: 1.0