For operation in the respective modes, please refer to the table LED buttons Operation / Programming.
Button LED Operation / Programming
LED
State
Operation in operation mode
Button LED 1
Press briefly
Long press (>3s)
Operation in programming mode
Button LED 1
Press briefly
Long press (>3s)
No operation for 45 seconds
Operation in query mode
Button LED 1
Press briefly
Long press (>3s)
No operation for 45 seconds
Sample programming
Further sample programming can be found in chapter "Sample programming [} 52]".
Behavior of the outputs when the settings are changed
If settings are changed during operation (outputs are switched on), the outputs remain switched on.
This has the advantage that the system can remain in operation and a change can be made "on-
line".
EL922x
Meaning
Switching output 1 on and off or resetting it
Activating the programming or query mode
Set nominal current value for output 1, press 1x = 1 A, press 2x = 2 A etc. up to
press 10x = 10 A, press more than 11x = OFF
For variants up to 4 A, press more than 5x = OFF applies
Saving the nominal current value and leaving the programming mode
After 45 seconds, the programming mode is automatically exited without saving
the settings.
No function
Exiting the query mode
After 45 seconds, the settings query mode is automatically exited again
Version: 1.0