Fig. 37 Exemplary Wiring Of An Input Voltage Of The El9221-5000 To Another Terminal - Beckhoff EL922 Series Documentation

Electronic overcurrent protection terminals
Table of Contents

Advertisement

Fig. 37: Exemplary wiring of an input voltage of the EL9221-5000 to another terminal.
3. Configuration
Create a configuration in the TwinCAT System Manager by manually inserting the terminal or scan-
ning it online. Please refer to the TwinCAT installation chapter [} 64].
EtherCAT XML Device Description
If the XML description of the EL922x is not available in your system you can download the latest
XML file from the download area of the Beckhoff website and install it according to the installation
instructions.
4. Commissioning
Observe the notes on operation and configuration using the LED buttons [} 41], as described in chap-
ter Mounting and wiring [} 41].
Checking of the process data (hardware protection) and the Diag messages
Check the process data [} 106] (hardware protection) and the Diag messages [} 151] for warnings
that could indicate a wiring error. Also check the Ready LED and the Button LEDs for flickering. The
terminal must not be operated in such a condition as this could destroy the electronics.
There are two options for setting the respective parameters, either via CoE or via the "Settings" tab.
Settings via CoE
The respective parameters should be set as usual in index 8000. Settings for channel 1 index 8000:0,
manual characteristic curve for channel 1 index 8001:0 (EL9227), settings for channel 2 index 8010:0,
manual characteristic curve for channel 2 index 8011:0 (EL9227).
EL922x
Version: 1.0
Commissioning
59