7.6.3.4
Configuration data (vendor-specific)
Index 80nF vendor data (for n = 0, ch.1; n = 1, ch. 2)
Index (hex) Name
80nF:0
Vendor data
80nF:11
Voltage In Calibration
Offset
80nF:12
Voltage In Calibration
Gain
80nF:13
Voltage Out Calibra-
tion Offset
80nF:14
Voltage Out Calibra-
tion Gain
80nF:15
Current Calibration
Offset
80nF:16
Current Calibration
Gain
80nF:17
Default Nominal Cur-
rent
80nF:18
Max Nominal Current Maximum nominal current
80nF:19
Nominal Current Type Nominal current adjustment option: adjustable or
7.6.3.5
Input data
Index 60n0 Inputs (for n = 0, Ch.1; n = 1, Ch. 2)
Index (hex) Name
60n0:0
Inputs
60n0:01
Status__Enabled
60n0:02
Status__Tripped
60n0:03
Status_Short Circuit
60n0:04
Status__Overload
60n0:05
Status__Hardware
Protection
60n0:06
Status__Overvoltage Overvoltage (input voltage ≥ 32 V DC)
60n0:07
Status__Undervoltage Undervoltage value reached or undershot
60n0:08
Status__Current
Level Warning
60n0:09
Status__Cool Down
Lock
60n0:0A
Status_Disabled By
Switch
60n0:0B
Status__Disabled By
DI
60n0:0C
Status__Disabled By
Output
60n0:0D
Status__Diag
60n0:0E
Status__TxPDO State Validity of the data of the associated TxPDO (0 =
60n0:0F
Status__Input Cycle
Counter
60n0:13
Status__Error
60n0:14
Status__State Reset
60n0:15
Status__State Switch Status Switch-Signal: Feedback for 70n0:02
60n0:21
Load
60n0:22
Current
60n0:23
Voltage In
60n0:24
Voltage Out
134
Meaning
Max. Subindex
Input voltage offset (vendor calibration)
Input voltage gain (vendor calibration)
Output voltage offset (vendor calibration)
Output voltage gain (vendor calibration)
Current offset (vendor calibration)
Current gain (vendor calibration)
Nominal current at delivery or after reset to factory
settings
fixed
Meaning
Max. Subindex
Channel switched on
Channel tripped
Short circuit (fault current ≥ 1.5 x I
Overload (fault current ≥ 1.1 x I
Hardware protection for overtemperature, reverse
feed, wiring error and redundant current measure-
ment, is displayed as long as the state is active
Current warning: prewarning info if the current has
reached or exceeded the prewarning threshold.
Restart lock (cooling time)
Channel switched off with button
Channel switched off through digital input
Channel switched off through process data output
Indicates that a new message is available in the
"Diag History"
valid, 1 = invalid)
2-bit counter for synchronization (incremented only if
a new value is present)
General hardware error
Status reset signal; feedback for 70n0:01
Load in % based on I
N
Output current in 0.01 A
Input voltage in 0.1 V
Output voltage in 0.1 V
Version: 1.0
Data type
UINT8
INT16
UINT16
INT16
UINT16
INT16
UINT16
UINT16
UINT16
UINT16
Data type
UINT8
BOOLEAN
BOOLEAN
)
BOOLEAN
N
)
BOOLEAN
N
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BIT2
BOOLEAN
BOOLEAN
BOOLEAN
UINT16
UINT16
UINT16
UINT16
Flags
Default
RO
0x19 (25
)
dec
RW
0x0000 (0
)
dec
RW
0x4000 (16384
)
dec
RW
0x0000 (0
)
dec
RW
0x4000 (16384
)
dec
RW
0x0000 (0
)
dec
RW
0x4000 (16384
)
dec
RW
---
RW
---
RW
---
Flags
Default
RO
0x24 (36
)
dec
RO
0x00 (0
)
dec
RO
0x00 (0
)
dec
RO
0x00 (0
)
dec
RO
0x00 (0
)
dec
RO
0x00 (0
)
dec
RO
0x00 (0
)
dec
RO
0x00 (0
)
dec
RO
0x00 (0
)
dec
RO
0x00 (0
)
dec
RO
0x00 (0
)
dec
RO
0x00 (0
)
dec
RO
0x00 (0
)
dec
RO
0x00 (0
)
dec
RO
0x00 (0
)
dec
RO
0x00 (0
)
dec
RO
0x00 (0
)
dec
RO
0x00 (0
)
dec
RO
0x00 (0
)
dec
RO
0x0000 (0
)
dec
RO
0x0000 (0
)
dec
RO
0x0000 (0
)
dec
RO
0x0000 (0
)
dec
EL922x