Beckhoff EL922 Series Documentation page 133

Electronic overcurrent protection terminals
Table of Contents

Advertisement

Index
Name
(hex)
80n0:0
DIG Safe State
Active
80n0:01
Active
Index 80n1 DIG Safe State Value Ch.n
(n=2 for Ch.1; n=3 for Ch.2
Index
Name
(hex)
80n1:0
DIG Safe State
Value
80n1:01
Value
7.6.3.3
Command object
Index B000 Command
Index (hex) Name
B000:0
Command
B000:01
Request
B000:02
Status
B000:03
Response
EL922x
Meaning
Maximum subindex
Enabling of the output state defined in
index 0x80n1:01 in case of a bus error
0: output retains its current state.
1: output is switched to the state defined in
index 0x80n1.
Meaning
Maximum subindex
Defines the state of the output in case of a
bus error:
0: output off
1: output on
Meaning
Max. Subindex
Commands can be sent to the terminal via the re-
quest object
Status of the command currently being executed
• 0: Command executed without error
• 255: Command is being executed
Optional return value of the command
Version: 1.0
Commissioning
Data type Flags Default value
UINT8
RO
0x01 (1
BOOLEAN RW
0x01 (1
Data type Flags Default value
UINT8
RO
0x01 (1
BOOLEAN RW
0x00 (0
Data type
Flags
Default
UINT8
RO
0x03 (3
OCTET-
RW
{0}
STRING[2]
UINT8
RO
0x00 (0
OCTET-
RO
{0}
STRING[6]
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
133