Roland R1000 Series Manual page 90

Double sheet control system with integrated fieldbus interface
Hide thumbs Also See for R1000 Series:
Table of Contents

Advertisement

Start-up
System parameter 16: Programming the "Measurement start" inputs under external control.
system parameter: 16
external meas. start
Fig. 80: Adjusting the measurement start inputs
Selectable operating conditions:
IN0:
IN0 + IN1:
IN0 + IN1 + IN2:
System parameter 17: Setting the output logic
system parameter: 17
output 0-1-2-warning
24V active
Fig. 81: Setting the output logic
Selectable options:
0 V:
+24 V: The outputs 0-sheet, 1-sheet, 2-sheet and warning are inverted, i.e. the respective
System parameter 18: Storing the active program number.
system parameter: 18
storage of active
program number
Fig. 82: Storing the active program number
Selectable options:
no:
yes:
90
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Double Sheet Control System R1000 series L20
with integrated fieldbus interface
IN0
If 24 VDC is applied to IN0, then the measurement is executed.
If 0 VDC is applied to this input then the measurement is stopped.
The measurement is performed only, if 24 VDC is applied
simultaneously to IN0 and IN1.
The measurement takes place only, if 24 VDC is applied
simultaneously to IN0 and IN1 and IN2.
(0-sheet, 1-sheet, 2-sheet and warning outputs).
As shown in the timing diagrams and the wiring diagrams
signals in the timing diagrams and wiring diagrams must be seen inverted.
Note
The output "Enable" is not affected thereby.
no
When the program is switched via Fieldbus or I/O, the program number will not be
stored. So the system always starts up at "Power up" with the program 255.
When the program is switched via Fieldbus or I/O, the program number will be
stored. So the system always starts up at "Power up" with the last selected program
by keyboard.
Attention
If the program is often stored, the memory becomes loaded with
frequent writing cycles and thus will be destroyed in the course of
time (lifetime is approx. 1.000.000 write cycles).
In this case „no" should be selected here.
Manual
B0063191 / 1.3