Roland R1000 Series Manual page 79

Double sheet control system with integrated fieldbus interface
Hide thumbs Also See for R1000 Series:
Table of Contents

Advertisement

B0063191 / 1.3
adjust parameter: 2
feed sheet 0.500 mm
for calibration
Push ENTER to start
Fig. 49: Prompt for placing the calibration sheet
The thickness of the calibration sheet is now displayed.
L20-XX-S: At this point place the calibration sheet in the measuring station. The calibration is
performed on one selected point. During the calibration a sheet must be between the sensors.
L20-3-XX-S: Now the calibration sheet is placed in the measuring station or passed through the
measuring station. Confirm by pressing the ENTER key.
L20-XX-S
adjust parameter: 2
control with
calibration sheet
Fig. 50: Select control with the calibration sheet Fig. 50: Display of the deviation
L20-XX-S:
If the control with the calibration
sheet was successful the message
above will be displayed.
The control is completed by pressing
the ENTER key.
Adjustment parameter 3: not available.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Double Sheet Control System R1000 series L20
with integrated fieldbus interface
Note
For L20-3-XX-S, the dynamic calibration is advantageous because
localized thickness variations or fluctuations in the calibration piece
will have less impact on the calibration.
L20-3-XX-S: The deviation is shown as a result.
ok
Manual
adjust parameter: 2
max. deviation
+/- 0.31mm
AB1 Ist: +0.01mm
L20-3-XX-S:
Deviations may occur due to thermal expansions of the
mechanic components.
The measured fault is taken in consideration in the
measuring result.
By large or in the case of large deviations a re-calibration
will be necessary.
Start-up
79