Fault messages, causes and remedies
9.5

Fieldbus interface faults

No.
Cause
70
The fieldbus function is not possible to perform, because
another field bus function is active at the same time
(/parallel function (IO) active and another parallel function
(IO)), e.g. "Measurement start" and "Program switching".
71
The selected sensor is not available for the function.
73
The activated fieldbus function (IO) is not possible or
disabled in the system configuration.
76
The fieldbus function is not possible, because the
measuring mode is set to "demo mode".
77
The fieldbus function is not possible, because the menu
(keyboard operation) is operational.
78
The fieldbus function cannot be executed, because the
equipment detected double sheet (with configuration
"double sheet hold").
79
The selected IP address / baud rate / Subnet / Gateway is
not conclusive.
80
The inserted fieldbus coupler is defective.
81
The commands come too fast via the parameter channel.
82
The fieldbus function is not possible to perform, because a
parallel PLC function is active , for instance, measurement
start" via Fieldbus and in addition "measurement start" via
parallel IO.
83
The parallel function (IO) is not possible to perform,
because a Fieldbus function is active.
84
Only L20-3-XX-S: While triggering calibration via interface
the range bit is not set.
88
The program number activated in the menu program
selection is > 255.
89
The fieldbus function cannot be executed, because the
parameter channel is active.
103
These faults match with the faults 3 resp.11-39 and may appear if data transmission from fieldbus via the
parameter channel is faulty.
111 - 139
104
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Double Sheet Control System R1000 series L20
with integrated fieldbus interface
Manual
Remedy
Implement only one function.
Check whether the correct bit is selected via the
Fieldbus.
If the function is required, then it should be
selected under systems configuration.
Configure the parameter "measurement operation"
to "external continuous measurement" or "external
single measurement".
Terminate the operation via the keyboard and
return the unit with the MENU key to its basic
mode.
Clear double sheet condition via fieldbus or via
keyboard.
Check IP-address / Baud rate / SubNet / Gateway
Recycle power, if the fault persists send the
equipment to Roland Electronic Service
Department
Always wait for the results of the parameter
channel transmission before transferring new data.
Avoid simultaneous operation.
Only L20-3-XX-S: Dynamic calibration, see
chapter 6.3.8. Set range bit.
Select valid program number.
Close Parameter channel.
B0063191 / 1.3