Communication with the PLC
6.5.1
Signal "Enable"
The signal "ENABLE" corresponds with the two process channel signals BOUT "Ready" and BOUT
"Function fault" according to the following boolean function:
ENABLE = BOUT Ready
BOUT
Ready
BOUT
Function fault
Fig. 25: Boolean function "ENABLE"
If the signal BOUT "Ready" is reset, then a fault has occurred, which requires a user intervention at
the control unit. Possible causes: memory faults, missing or too low voltages.
6.5.2
Signal "Warning"
The "Warning" signal is an additional output signal with fixed evaluation thresholds.
The signal becomes activated if the measurement result is below 80% or above 120% of the preset
nominal value.
56
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Double Sheet Control System R1000 series L20
with integrated fieldbus interface
BOUT Function fault
&
ENABLE
Note
The timing diagrams in the sections "6.5.3" and "6.5.4" do not contain an
explicit chart of the signal "ENABLE".
Note
The signal will also be activated if measurements without a sheet
(measurement value below 80%) are performed.
Manual
B0063191 / 1.3