Roland R1000 Series Manual page 49

Double sheet control system with integrated fieldbus interface
Hide thumbs Also See for R1000 Series:
Table of Contents

Advertisement

B0063191 / 1.3
Inputs (PLC  L20)
Byte.Bit
Meaning
Service selection (Bit 32,1,0)
BIN0.0
0000 = empty service
BIN0.1
0001 = read parameters
0010 = write parameters
BIN0.2
0100 = open parameter channel
1000 = close parameter channel
BIN0.3
BIN0.4
Set Application data length always to
11 (11 = 4 Byte)
BIN0.5
Handshake The state is changed with
every new job. It is controlled by the
master only, when a new job is to be
processed by the R1000. The R1000
mirrors the handshake back, once the job
BIN0.6
is processed. At a successful job, the
collision bit is set to 0, otherwise the
collision bit is set by the R1000 to 1.
Further jobs can only be done by
withdrawal of the faulty service.
BIN0.7
--
Program index
BIN1.0-7
Back reflexion
0 = Program 1, 255 = System parameter
Parameter index
0...255,
BIN2.0-7
Assignment see section 11.1
"Parameter channel commands"
BIN3.0-7
Application data byte 0 (MSB)
BIN4.0-7
Application data byte 1
BIN5.0-7
Application data byte 2
BIN6.0-7
Application data byte 3 (LSB)
BIN7.0-7
Checksum
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Double Sheet Control System R1000 series L20
with integrated fieldbus interface
Manual
Outputs (L20  PLC)
Byte.Bit
Meaning
Service selection (Bit 3,2,1,0)
BOUT0.0
0000 = empty service
BOUT0.1
0001 = read parameters
0010 = write parameters
BOUT0.2
0100 = open parameter channel
1000 = close parameter channel
BOUT0.3
BOUT0.4
Set Application data length always to
11 (11 = 4 Byte)
BOUT0.5
Handshake The state is changed with every
new job. It is controlled by the master only,
when a new job is to be processed by the
R1000. The R1000 mirrors the handshake
back, once the job is processed. At a successful
BOUT0.6
job, the collision bit is set to 0, otherwise the
collision bit is set by the R1000 to 1. Further
jobs can only be done by withdrawal of the
faulty service.
Collision
0 = Fault free access, 1 = Faulty access.
"1" is set by the R1000 only if a service is
BOUT0.7
invalid or not executable. In this case the
master must reset the service to end the faulty
condition. See also the section "Reset faulty
access" within this chapter.
Program index
BOUT1.0-7
0 = Program 1, 255 = System parameter
Parameter index
1 ... 18 at program parameter
BOUT2.0-7
1 ... 24 at system parameter
Assignment see section 11.1
"Parameter channel commands"
BOUT3.0-7
Application data byte 0 (MSB)
BOUT4.0-7
Application data byte 1
BOUT5.0-7
Application data byte 2
BOUT6.0-7
Application data byte 3 (LSB)
BOUT7.0-7
Checksum
Communication with the PLC
49