Between signal AnOut1(2) in Volt, which is internally generated after configuring analog output OUT 1 or
OUT 2 as desired and which is displayed by parameters M019 and M020 respectively, and outgoing signal
I
in mA, the following relation is to be applied:
out
AnOut1(2)=10V  I
Before generating signal AnOut1(2), the Gain and Bias functions may be used (followed by the Polarity
function) starting from signals V
AnOut
With the default values of the relevant parameters, the final matching between V
V
=0V
out
V
=2V
out
V
=10V
out
The table below shows the values to be assigned to the different parameters relating to the Gain and Bias
functions to obtain a particular signal I
assumes that the parameters relating to the Polarity function (par. P157 and P158) are at their default
value.
V
I
out
out
0 ... 10V
0 ... 20mA
0 ... 10V
4 ... 20mA
10 ... +10V
0 ... 20mA
10 ... +10V
4 ... 20mA
=20mA
out
originally configured, according to the formula below:
out1(2)
Gain
Bias
V
10
out
100
100
I
=0mA
out
I
=4mA
out
I
=20mA
out
in mA, starting from internal signal V
out
Jumper JP4010
in the control board
in pos. 2-3
OUT 1 [Terminal 8]
Gain
P152 = 100%
P152 = 80%
P152 = 50%
P152 = 40%
Bias
Gain
P151 = 0%
P155 = 100%
P151 = 20%
P155 = 80%
P151 = 50%
P155 = 50%
P151 = 60%
P155 = 40%
15P0059B3
USER MANUAL
and I
is the following:
out
out
in Volt. The table
out
Jumper JP409
in the control board
in pos. 2-3
OUT 2 [Terminal 10]
Bias
P154 = 0%
P154 = 20%
P154 = 50%
P154 = 60%
73/200