W009: Wrong Parameters In Eeprom Backup Area - Santerno DCREG2 Series User Manual

Table of Contents

Advertisement

DCREG2
DCREG4
8.2.8 W009: W
RONG
W008 EEPROM
WorkArea Failure
P
ARAMETERS IN
I
W009 - EEPROM Backup Area Fail.
This warning may pop up after resetting Alarm A026 (EEPROM BackupArea
S
Fail.). It indicates that the work area copy to the EEPROM work area has failed
due to the alteration of the work area values. In general, the equipment may be
normally started, but we suggest that the default values be entered through the
P002  1:DefaultRestore if the values saved in the work area do not
correspond to the values required. Then, manually store the parameter values
noted down at the end of the startup procedure. Always copy these values in the
backup area through the P002  2:WorkAreaBackup command (the warning
will disappear). See also the PARAMETER COPY chapter.
EEPROM B
ACKUP
15P0059B3
USER MANUAL
A
REA
193/200